The GV2ME14K1BW3 is a non-reversing DOL combination starter from the TeSys GV2-ME series, integrating a motor circuit breaker and a 3-pole contactor in one block with a GV2AF01 auxiliary contact block. It provides coordinated motor starting and overload protection in a single DIN-rail footprint. The thermal protection adjustment range is 6...10 A, and the magnetic tripping current is fixed at 138 A, meaning short-circuit protection trips at roughly 14–23 times the thermal setting. The control circuit runs on 24 V DC. Coordination is Type 1, so after a fault the starter may need replacement but the upstream device stays intact.
Motor power coverage
Rated motor power spans 3 kW to 5.5 kW depending on supply voltage: 3 kW at 400/415 V, 4 kW at 400/415 V, 440 V, or 500 V, and 5.5 kW at 500 V.
Sourcing reality — obsolete part
If a direct replacement is needed, a parametric match based on the 6...10 A thermal range, 24 V DC coil, and 3-pole configuration would be the starting point for a cross-reference search.
The unit measures 45 mm wide, 152 mm high, and 87 mm deep — a standard 45 mm modular width that fits a single DIN-rail pitch. Panel layout should account for the depth to ensure clearance against the gland plate or back wall.