Skip to main content
Schneider Electric GV2ME14K1F7 — Miniature Circuit Breakers (MCB)

Schneider TeSys GV2ME14K1F7 Motor Starter, 6-10 A, 110 V AC

MPNGV2ME14K1F7
Active

Schneider Electric TeSys GV2-ME series, GV2ME14K1F7, DOL combination motor starter, 6...10 A thermal adjustment, 110 V AC 50/60 Hz control voltage.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

GV2ME14K1F7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter

Ratings

GV2ME14K1F7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 15 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 6 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3

Mechanical

GV2ME14K1F7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm

Other specifications

GV2ME14K1F7 — Other specifications
ParameterValue
Motor power3 kW at 400/415 V AC 50/60 Hz 4 kW at 400/415 V AC 50/60 Hz 4 kW at 440 V AC 50/60 Hz 4 kW at 500 V AC 50/60 Hz 5.5 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 combination block GV2AF01 1 motor circuit breaker type GV2ME 1 3-pole contactor
Motor starter typeNon reversing
Magnetic tripping current138 A
Coil voltage110 V AC 50/60 Hz
Thermal protection adjustment range6...10 A

Product details

The GV2ME14K1F7 is a non-reversing DOL combination motor starter from the TeSys GV2-ME range, built as a single block that pairs a 3-pole motor circuit breaker with a 3-pole contactor and the GV2AF01 combination block. It covers motor protection from 6 to 10 A via the adjustable thermal relay, and the magnetic trip is fixed at 138 A — so it catches a locked-rotor condition on a motor sized within that band without nuisance-tripping on startup inrush. Rated for AC-3 utilisation category, meaning it is designed for switching squirrel-cage induction motors — starting, stopping, and reversing under load. The motor power rating hits 3 kW at 400/415 V AC and goes up to 5.5 kW at 500 V AC, so it fits common European 400 V line-fed pumps, fans, and small conveyors.

At 440 V it drops to 15 kA, and at 500 V to 6 kA, so on a 480 V line (common in North American retrofit) you need to verify the available fault current at the panel.

Panel fit and sourcing

Dimensions are 152 mm high, 45 mm wide, 87 mm deep — the 45 mm width is a single modular DIN space, so it clips onto standard 35 mm DIN rail inside a control cabinet. The control circuit runs on 110 V AC 50/60 Hz, which matches common panel control transformers in European and Middle East installations; if your site runs 24 V DC or 230 V control, you need a different coil variant in the GV2ME family.

Frequently asked questions

What is the thermal protection adjustment range?

The adjustable thermal overload relay covers 6 to 10 A, set via a dial on the front of the breaker block.

What breaking capacity does it offer at 400 V?

It is rated for 50 kA at 400/415 V AC per IEC 60947-4-1, which covers most industrial distribution panels with a transformer upstream.

Does it include both a breaker and a contactor in one unit?

Yes, it is a combination starter: one GV2ME motor circuit breaker, one 3-pole contactor, and the GV2AF01 interlock block assembled as a single DIN-rail mountable device.

MPN
GV2ME14K1F7