Skip to main content
Schneider Electric GV2ME14K1FE7 — Molded Case Circuit Breakers (MCCB)

Schneider GV2ME14K1FE7 TeSys DOL Starter, 6-10 A, 115 V AC

MPNGV2ME14K1FE7
Active

Schneider Electric TeSys GV2-ME DOL combination starter, GV2ME14K1FE7, 6-10 A thermal adjustment, 115 V AC 50/60 Hz control voltage.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2ME14K1FE7 — Identification
ParameterValue
Product / component typeMotor starter
GV2ME14K1FE7 — Mechanical
ParameterValue
Height152 mm
Width45 mm
Depth87 mm
GV2ME14K1FE7 — Electrical
ParameterValue
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 15 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 6 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
GV2ME14K1FE7 — Specifications
ParameterValue
Poles description3P
Device short nameGV2ME
GV2ME14K1FE7 — Other specifications
ParameterValue
RangeTeSys
Motor power3 kW at 400/415 V AC 50/60 Hz 4 kW at 400/415 V AC 50/60 Hz 4 kW at 440 V AC 50/60 Hz 4 kW at 500 V AC 50/60 Hz 5.5 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device composition1 combination block GV2AF01 1 motor circuit breaker type GV2ME 1 3-pole contactor
Motor starter typeNon reversing
Utilisation categoryAC-3
Magnetic tripping current138 A
Coil voltage115 V AC 50/60 Hz
Thermal protection adjustment range6...10 A

Product details

The GV2ME14K1FE7 is a non-reversing DOL combination starter from the TeSys GV2-ME range, integrating a 3-pole motor circuit breaker and a 3-pole contactor into a single block with the GV2AF01 combination block. The thermal protection adjustment range of 6-10 A sets the overload trip point for the motor, while the magnetic tripping current of 138 A handles short-circuit protection. Rated for AC-3 utilisation category, this starter is designed for direct-on-line starting of three-phase squirrel-cage induction motors. Motor power ratings span 3 kW at 400/415 V up to 5.5 kW at 500 V AC, making it suitable for pumps, fans, compressors, and conveyors in industrial control panels. The 45 mm width and 152 mm height fit standard DIN-rail enclosures with typical panel fill factors.

The 6-10 A thermal adjustment range is the overload setting you dial in to match the motor's full-load current. Set it at the motor nameplate FLA — the magnetic trip at 138 A is fixed and handles short-circuits only, not overloads. Coordination is Type 1, meaning the starter may need contactor replacement after a fault, but the breaker resets. The 115 V AC control voltage is the coil rating. The depth of 87 mm matters when fitting into shallow enclosures or when gland plates limit rear clearance.

Frequently asked questions

What replaces the GV2ME14K1FE7?

No official successor order code is listed in the lifecycle record. For a direct replacement, you would need to evaluate current TeSys GV3P or GV4P motor starters with similar ratings (6-10 A thermal, 115 V AC coil) and adjust the panel layout accordingly.

How do I source this obsolete part?

We source the GV2ME14K1FE7 to order against an RFQ from surplus and broker inventory. Submit your quantity for a quote — this covers you while remaining stock lasts.

What are the key ratings for fit verification?

Thermal protection adjustment range 6-10 A, magnetic tripping current 138 A, control circuit voltage 115 V AC 50/60 Hz, breaking capacity 50 kA at 400/415 V AC (IEC 60947-4-1), and motor power up to 5.5 kW at 500 V AC.

MPN
GV2ME14K1FE7