The GV2ME14K1FE7 is a non-reversing DOL combination starter from the TeSys GV2-ME range, integrating a 3-pole motor circuit breaker and a 3-pole contactor into a single block with the GV2AF01 combination block. The thermal protection adjustment range of 6-10 A sets the overload trip point for the motor, while the magnetic tripping current of 138 A handles short-circuit protection. Rated for AC-3 utilisation category, this starter is designed for direct-on-line starting of three-phase squirrel-cage induction motors. Motor power ratings span 3 kW at 400/415 V up to 5.5 kW at 500 V AC, making it suitable for pumps, fans, compressors, and conveyors in industrial control panels. The 45 mm width and 152 mm height fit standard DIN-rail enclosures with typical panel fill factors.
The 6-10 A thermal adjustment range is the overload setting you dial in to match the motor's full-load current. Set it at the motor nameplate FLA — the magnetic trip at 138 A is fixed and handles short-circuits only, not overloads. Coordination is Type 1, meaning the starter may need contactor replacement after a fault, but the breaker resets. The 115 V AC control voltage is the coil rating. The depth of 87 mm matters when fitting into shallow enclosures or when gland plates limit rear clearance.