Schneider Electric GV2ME14K1M7 — Miniature Circuit Breakers (MCB)

Schneider Electric GV2ME14K1M7 TeSys DOL Starter, 6-10 A, 22

MPNGV2ME14K1M7
Obsolete

Schneider Electric TeSys GV2-ME series, GV2ME14K1M7, DOL combination starter, 6...10 A, 220...230 V AC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

GV2ME14K1M7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter

Ratings

GV2ME14K1M7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 15 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 6 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3

Mechanical

GV2ME14K1M7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm

Other specifications

GV2ME14K1M7 — Other specifications
ParameterValue
Motor power3 kW at 400/415 V AC 50/60 Hz 4 kW at 400/415 V AC 50/60 Hz 4 kW at 440 V AC 50/60 Hz 4 kW at 500 V AC 50/60 Hz 5.5 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 motor circuit breaker type GV2ME 1 3-pole contactor 1 combination block GV2AF01
Motor starter typeNon reversing
Magnetic tripping current138 A
Coil voltage220/230 V AC 50/60 Hz
Thermal protection adjustment range6...10 A

Product details

The GV2ME14K1M7 is a non-reversing DOL combination starter from the TeSys GV2-ME range, integrating a GV2ME motor circuit breaker, a 3-pole contactor, and a GV2AF01 combination block into one unit. It provides thermal and magnetic protection for three-phase motors, with a thermal adjustment range of 6 to 10 A and a magnetic tripping threshold of 138 A. Rated for AC-3 utilisation category, it handles motor switching duty at up to 5.5 kW on 500 V AC supply, with breaking capacity reaching 50 kA at 400/415 V AC per IEC 60947-4-1.

Breaking capacity of 50 kA at 400/415 V AC means this starter can safely interrupt a fault current up to that level without upstream damage, provided the coordination type (Type 1) is acceptable for your panel — Type 1 allows the starter to be damaged after a fault, requiring replacement.

It is a self-contained unit: wire the incoming three-phase supply to the breaker input, the motor leads to the contactor output, and the control voltage (220/230 V AC) to the coil terminals.

Frequently asked questions

What are the key ratings for this motor starter?

Thermal adjustment range 6-10 A, magnetic trip at 138 A, control voltage 220/230 V AC 50/60 Hz, breaking capacity 50 kA at 400/415 V AC (IEC 60947-4-1), and motor power up to 5.5 kW at 500 V AC.

How do I source this obsolete part?

Since it is obsolete, sourcing is through surplus or independent distributor channels. Submit an RFQ for current availability and pricing; it is not stocked as a standard production item.

MPN