Skip to main content
Schneider Electric GV2ME14K1Q7 — Miniature Circuit Breakers (MCB)

Schneider GV2ME14K1Q7 TeSys DOL Starter, 6-10 A, 380-400V

MPNGV2ME14K1Q7
Active

Schneider Electric TeSys GV2-ME DOL combination starter, GV2ME14K1Q7, 6...10 A thermal adjustment, 380...400 V AC control voltage.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

GV2ME14K1Q7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter

Ratings

GV2ME14K1Q7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 15 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 6 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3

Mechanical

GV2ME14K1Q7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm

Other specifications

GV2ME14K1Q7 — Other specifications
ParameterValue
Motor power3 kW at 400/415 V AC 50/60 Hz 4 kW at 400/415 V AC 50/60 Hz 4 kW at 440 V AC 50/60 Hz 4 kW at 500 V AC 50/60 Hz 5.5 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 combination block GV2AF01 1 3-pole contactor 1 motor circuit breaker type GV2ME
Motor starter typeNon reversing
Magnetic tripping current138 A
Coil voltage380/400 V AC 50/60 Hz
Thermal protection adjustment range6...10 A

Product details

The GV2ME14K1Q7 is an active-production TeSys GV2-ME direct-on-line (DOL) combination starter from Schneider Electric. It integrates a 3-pole motor circuit breaker and a 3-pole contactor into a single block, using the GV2AF01 auxiliary contact block for feedback. The thermal protection adjustment range is 6...10 A, and the control circuit voltage is 380/400 V AC 50/60 Hz — so it's a self-contained unit for starting and protecting a three-phase motor on a 400 V line.

The magnetic tripping current is 138 A, meaning the instantaneous magnetic release will trip on a short-circuit or high-inrush condition above that level, protecting the motor and downstream wiring. At 440 V the breaking capacity drops to 15 kA, and at 500 V to 6 kA, so the supply voltage matters for SCCR coordination. Motor power ratings are 3 kW at 400/415 V and up to 5.5 kW at 500 V, all in AC-3 utilisation category (starting squirrel-cage motors, switching off running motors). The coordination type is Type 1, meaning after a fault the starter may need contact replacement, but the panel and cables stay intact.

The 45 mm width (3 module spaces) means it fits in a typical distribution board without crowding adjacent devices. The depth of 87 mm is the dimension that matters for enclosure depth clearance; most 120 mm deep enclosures will accommodate it with room for wiring.

Frequently asked questions

What are the key ratings for fit?

Thermal protection adjustment 6...10 A, control voltage 380/400 V AC, magnetic trip at 138 A, breaking capacity 50 kA at 400 V (IEC 60947-4-1), and motor power 3 kW at 400/415 V in AC-3 duty.

What is the depth of this starter?

The depth is 87 mm, which is the dimension that matters for enclosure clearance.

MPN
GV2ME14K1Q7