Skip to main content
Schneider Electric GV2ME14K1U7 — Miniature Circuit Breakers (MCB)

Schneider GV2ME14K1U7 DOL Starter, 6-10 A, 230/240 V AC, Obs

MPNGV2ME14K1U7
Obsolete

Schneider Electric TeSys GV2-ME DOL combination starter, GV2ME14K1U7, 6-10 A thermal protection, 230/240 V AC control, obsolete.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

GV2ME14K1U7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter

Ratings

GV2ME14K1U7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 15 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 6 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3

Mechanical

GV2ME14K1U7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm

Other specifications

GV2ME14K1U7 — Other specifications
ParameterValue
Motor power3 kW at 400/415 V AC 50/60 Hz 4 kW at 400/415 V AC 50/60 Hz 4 kW at 440 V AC 50/60 Hz 4 kW at 500 V AC 50/60 Hz 5.5 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 motor circuit breaker type GV2ME 1 3-pole contactor 1 combination block GV2AF01
Motor starter typeNon reversing
Magnetic tripping current138 A
Coil voltage230/240 V AC 50/60 Hz
Thermal protection adjustment range6...10 A

Product details

The GV2ME14K1U7 is a non-reversing DOL combination starter from the Schneider TeSys GV2-ME series. It integrates a motor circuit breaker (thermal-magnetic), a 3-pole contactor, and a combination block (GV2AF01) into one unit, sized for direct-on-line starting of three-phase induction motors. Thermal protection adjustment covers 6 to 10 A, with a magnetic trip set at 138 A. It is designed for AC-3 utilisation category (squirrel-cage motor starting/switching).

Breaking capacity is 50 kA at 400/415 V AC, dropping to 15 kA at 440 V and 6 kA at 500 V (all conforming to IEC 60947-4-1). This means the starter can safely interrupt a fault at those levels without upstream device damage — critical for SCCR compliance in a panel. Coordination is Type 1, so after a fault the starter may need replacement, but the upstream breaker holds. Motor power ratings: 3 kW at 400/415 V, 4 kW at 440 V, and 5.5 kW at 500 V (all 50/60 Hz). The 6-10 A thermal band matches motors drawing 6-10 A full-load; the magnetic trip at 138 A handles inrush without nuisance trips.

Schneider lists the GV2ME14K1U7 as obsolete. The part is sourced through surplus or broker channels; submit an RFQ for availability and pricing.

Frequently asked questions

What is the depth of GV2ME14K1U7?

The depth is 87 mm.

What is the product range for GV2ME14K1U7?

It belongs to the TeSys range.

MPN
GV2ME14K1U7