Skip to main content
Schneider Electric GV2ME14K2B7 — Miniature Circuit Breakers (MCB)

Schneider GV2ME14K2B7 TeSys Reversing Starter, 6-10 A, 24 V

MPNGV2ME14K2B7
Obsolete

Schneider Electric TeSys GV2-ME DOL reversing combination starter, GV2ME14K2B7, 6...10 A thermal protection, 24 V AC 50/60 Hz coil, 3-pole.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

GV2ME14K2B7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter

Ratings

GV2ME14K2B7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 15 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 6 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3

Mechanical

GV2ME14K2B7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm

Other specifications

GV2ME14K2B7 — Other specifications
ParameterValue
Motor power3 kW at 400/415 V AC 50/60 Hz 4 kW at 400/415 V AC 50/60 Hz 4 kW at 440 V AC 50/60 Hz 4 kW at 500 V AC 50/60 Hz 5.5 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 combination block GV2AF01 1 motor circuit breaker type GV2ME 1 3-pole reversing contactor
Motor starter typeReversing
Magnetic tripping current138 A
Coil voltage24 V AC 50/60 Hz
Thermal protection adjustment range6...10 A

Product details

The GV2ME14K2B7 is a DOL reversing combination starter from the TeSys GV2-ME range, integrating a motor circuit breaker, a 3-pole reversing contactor, and a GV2AF01 combination block into one assembly. It provides thermal protection adjustable from 6 to 10 A and magnetic short-circuit protection tripping at 138 A, all in a 45 mm wide, 152 mm high, 87 mm deep package that clips onto a DIN rail. Rated for AC-3 utilisation category, it handles motor loads up to 3 kW at 400/415 V AC, 4 kW at 440 V, and 5.5 kW at 500 V.

Breaking capacity is 50 kA at 400/415 V AC, 15 kA at 440 V, and 6 kA at 500 V, all conforming to IEC 60947-4-1. This is Type 1 coordination, meaning the starter may need contact replacement after a fault — acceptable for most industrial lines where uptime is restored by swapping the unit rather than clearing welded contacts.

Schneider Electric lists the GV2ME14K2B7 as obsolete. No official successor order code exists, so a direct form-fit-function replacement within the current TeSys range must be identified by comparing the thermal adjustment range (6-10 A), 24 V AC coil, reversing configuration, and DIN-rail footprint.

Frequently asked questions

What are the key ratings of the GV2ME14K2B7?

Thermal protection adjustment range is 6 to 10 A. Magnetic trip is at 138 A. Motor power ratings: 3 kW at 400/415 V, 4 kW at 440 V, 5.5 kW at 500 V. Breaking capacity is 50 kA at 400/415 V. Control voltage is 24 V AC 50/60 Hz.

How do I source the GV2ME14K2B7 now that it is obsolete?

This part is sourced through independent surplus and broker channels. Submit an RFQ for current availability and pricing — there is no standard lead time or stock position.

MPN