Skip to main content
Schneider Electric GV2ME14K2BW3 — Miniature Circuit Breakers (MCB)

Schneider GV2ME14K2BW3 TeSys Reversing Motor Starter, 6-10 A

MPNGV2ME14K2BW3
Obsolete

Schneider Electric TeSys GV2-ME, reversing DOL combination starter, GV2ME14K2BW3, 6-10 A thermal adjustment, 24 VDC coil, 3-pole.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

GV2ME14K2BW3 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter

Ratings

GV2ME14K2BW3 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 15 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 6 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3

Mechanical

GV2ME14K2BW3 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm

Other specifications

GV2ME14K2BW3 — Other specifications
ParameterValue
Motor power3 kW at 400/415 V AC 50/60 Hz 4 kW at 400/415 V AC 50/60 Hz 4 kW at 440 V AC 50/60 Hz 4 kW at 500 V AC 50/60 Hz 5.5 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 3-pole reversing contactor 1 motor circuit breaker type GV2ME 1 combination block GV2AF01
Motor starter typeReversing
Magnetic tripping current138 A
Coil voltage24 V DC
Thermal protection adjustment range6...10 A

Product details

The Schneider GV2ME14K2BW3 is a TeSys GV2-ME reversing DOL combination starter — a single unit that bundles a 3-pole reversing contactor, a GV2ME motor circuit breaker, and a GV2AF01 mechanical interlock block. The 24 VDC control coil means it drops into existing 24 VDC control circuits common in modern panels — no separate AC supply needed for the contactor. The magnetic trip is fixed at 138 A, so short-circuit protection is baked in; you don't add a separate magnetic element.

At 440 V it's 15 kA; at 500 V it drops to 6 kA — so if your line runs at 500 V, verify the available fault current stays under that ceiling. Coordination is Type 1, meaning the starter may need contact replacement after a fault but the panel stays intact.

Lifecycle reality

This part is marked obsolete by Schneider. Factory production has stopped; new supply comes from surplus or broker channels. For a qualified BOM line, this is a last-time-buy candidate.

Dimensions are 152 mm high, 45 mm wide, 87 mm deep — standard DIN-rail footprint for the TeSys GV2 series. The 45 mm width means it occupies three 15 mm modular spaces on the rail. Panel builders will find the depth manageable for standard 200 mm deep enclosures; just watch clearance for the coil terminals and the manual reset button on the front face.

Frequently asked questions

What is the thermal protection adjustment range?

The overload relay adjusts from 6 A to 10 A, set via the dial on the front of the GV2ME breaker.

What control voltage does the coil require?

24 V DC. The coil is built into the reversing contactor assembly, so no separate coil supply is needed.

What is the breaking capacity at 400 V?

50 kA at 400/415 V AC, per IEC 60947-4-1. That's enough for most industrial panel fault levels.

MPN
GV2ME14K2BW3