The Schneider Electric GV2ME14K2F7 is a DOL reversing combination starter from the TeSys GV2-ME series. It packages a 3-pole reversing contactor, a GV2ME motor circuit breaker, and a GV2AF01 mechanical interlock into one compact unit — one part number, one DIN-rail footprint, no wiring the interlock yourself. The thermal protection adjustment range is 6...10 A, with a fixed magnetic trip at 138 A. That magnetic setting is high enough to let the motor start without nuisance tripping on inrush but still clears a bolted fault fast. Rated for AC-3 duty (motor switching) at 3 kW on a 400/415 V supply, it also handles 4 kW at 440 V or 500 V, and pushes to 5.5 kW at 500 V. The 110 V AC control coil matches standard panel control transformers in many plants.
The GV2ME14K2F7 delivers 50 kA breaking capacity at 400/415 V AC, conforming to IEC 60947-4-1. Coordination is Type 1, meaning the starter may need contact replacement after a fault, but the upstream protection stays selective.