The Schneider Electric GV2ME14K2M7 is a DOL reversing combination motor starter from the TeSys GV2-ME range. It integrates a 3-pole motor circuit breaker with thermal and magnetic protection, a reversing contactor, and a GV2AF01 combination block into a single unit, so one order code covers the full reversing starter assembly for a panel. The thermal protection adjustment range is 6...10 A, which sets the overload trip point for the connected motor. The magnetic tripping current is fixed at 138 A, providing short-circuit protection that clears fast without waiting for the thermal element. Rated for AC-3 utilisation category, meaning it is designed for starting and stopping squirrel-cage induction motors under full load. The motor power ratings vary by supply voltage: 3 kW at 400/415 V AC, 4 kW at 440 V AC, and up to 5.5 kW at 500 V AC.
Breaking capacity is 50 kA at 400/415 V AC, 15 kA at 440 V AC, and 6 kA at 500 V AC, all conforming to IEC 60947-4-1. Coordination type is Type 1, so under a short-circuit fault the starter may require replacement of the contactor or breaker, but the installation is protected from fire or shock hazard. For applications where downtime must be minimised, a Type 2 coordinated assembly would be specified instead.
Control circuit and dimensions
Verify the control transformer or PLC output matches this voltage before wiring. Dimensions are 152 mm high, 45 mm wide, and 87 mm deep. The 45 mm width occupies three 15 mm DIN-rail module spaces, so plan enclosure fill accordingly.