Skip to main content
Schneider Electric GV2ME14K2Q7 — Molded Case Circuit Breakers (MCCB)

Schneider GV2ME14K2Q7 TeSys reversing motor starter, 6-10 A

MPNGV2ME14K2Q7
Active

Schneider Electric TeSys GV2-ME reversing combination motor starter, GV2ME14K2Q7, thermal protection 6...10 A, 380/400 V AC control, 3-pole.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2ME14K2Q7 — Identification
ParameterValue
Product / component typeMotor starter
GV2ME14K2Q7 — Mechanical
ParameterValue
Height152 mm
Width45 mm
Depth87 mm
GV2ME14K2Q7 — Electrical
ParameterValue
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 15 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 6 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
GV2ME14K2Q7 — Specifications
ParameterValue
Poles description3P
Device short nameGV2ME
GV2ME14K2Q7 — Other specifications
ParameterValue
RangeTeSys
Motor power3 kW at 400/415 V AC 50/60 Hz 4 kW at 400/415 V AC 50/60 Hz 4 kW at 440 V AC 50/60 Hz 4 kW at 500 V AC 50/60 Hz 5.5 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device composition1 combination block GV2AF01 1 3-pole reversing contactor 1 motor circuit breaker type GV2ME
Motor starter typeReversing
Utilisation categoryAC-3
Magnetic tripping current138 A
Coil voltage380/400 V AC 50/60 Hz
Thermal protection adjustment range6...10 A

Product details

The Schneider Electric GV2ME14K2Q7 is a TeSys GV2-ME reversing combination motor starter — a single-block assembly that combines a 3-pole motor circuit breaker (type GV2ME) with a reversing contactor and a GV2AF01 combination block. The thermal protection adjustment range of 6...10 A sets the overload relay's trip threshold, so you dial it to match the motor's full-load current. The magnetic short-circuit trip is fixed at 138 A — that's the instantaneous pickup that clears a fault without waiting for the thermal element. Rated for utilisation category AC-3, meaning it's tested for starting and stopping squirrel-cage motors — the standard duty for conveyor, pump, and fan loads.

The GV2ME14K2Q7 snaps onto a 45 mm wide DIN-rail footprint — standard for panel-mounting in motor control centres. The 152 mm height and 87 mm depth leave room for auxiliary contact blocks or a downstream contactor interlock on the same rail. The reversing contactor pair is internally interlocked; you just supply the forward/reverse signals.

Coordination and sourcing

This is a Type 1 coordinated starter per IEC 60947-4-1, meaning after a short-circuit the starter may need contactor replacement but the breaker self-protects.

Frequently asked questions

What is the thermal protection range and what does it mean?

The thermal adjustment range is 6...10 A. You set it to the motor's nameplate full-load current within that window. The magnetic trip is fixed at 138 A — that's the instantaneous short-circuit threshold, not adjustable.

What breaking capacity does this starter have?

50 kA at 400/415 V AC (IEC 60947-4-1), 15 kA at 440 V, and 6 kA at 500 V. At 400 V it's suitable for most industrial distribution panels without upstream current-limiting fuses.

What control voltage does the coil need?

The control circuit is 380/400 V AC 50/60 Hz — line voltage, same as the motor supply. No separate control transformer is required for the reversing contactor coil.

MPN