Schneider Electric GV2ME16K1F7 — Miniature Circuit Breakers (MCB)

Schneider Electric GV2ME16K1F7 TeSys DOL Starter, 9-14 A, 11

MPNGV2ME16K1F7
Active

Schneider Electric TeSys GV2-ME DOL combination starter, GV2ME16K1F7, 9-14 A thermal range, 110 V AC coil, 3-pole non-reversing.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

GV2ME16K1F7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter

Ratings

GV2ME16K1F7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity15 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 8 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 6 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3

Mechanical

GV2ME16K1F7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm

Other specifications

GV2ME16K1F7 — Other specifications
ParameterValue
Motor power5.5 kW at 400/415 V AC 50/60 Hz 5.5 kW at 440 V AC 50/60 Hz 7.5 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 combination block GV2AF01 1 motor circuit breaker type GV2ME 1 3-pole contactor
Motor starter typeNon reversing
Magnetic tripping current170 A
Coil voltage110 V AC 50/60 Hz
Thermal protection adjustment range9...14 A

Product details

The Schneider Electric GV2ME16K1F7 is a DOL (direct-on-line) combination starter from the TeSys GV2-ME range, integrating a motor circuit breaker and a 3-pole contactor in one block with a GV2AF01 auxiliary contact block. It's a non-reversing starter sized for AC-3 duty — the standard utilisation category for squirrel-cage induction motors — with a thermal protection adjustment range of 9 to 14 A. The magnetic trip is set at 170 A, which handles the inrush on a motor up to 5.5 kW at 400/415 V AC (or 7.5 kW at 500 V AC). Breaking capacity is 15 kA at 400/415 V per IEC 60947-4-1, with Type 1 coordination — meaning the starter can interrupt a fault up to that level, but the contactor may need replacement after a short-circuit event. For a panel builder, that's the trade-off: you get a compact unit (45 mm wide, 152 mm tall, 87 mm deep) that fits a standard DIN-rail enclosure, but plan for a spare contactor if the line feeds a high-fault-capacity bus.

Frequently asked questions

What are the key ratings for this starter?

Thermal adjustment range 9-14 A, magnetic trip 170 A, control voltage 110 V AC 50/60 Hz. Motor power: 5.5 kW at 400/415 V AC, 7.5 kW at 500 V AC. Breaking capacity 15 kA at 400/415 V AC per IEC 60947-4-1, Type 1 coordination.

What compliance documentation is available?

The product carries IEC 60947-4-1 certification for breaking capacity. RoHS and REACH compliance are standard for the TeSys range, but specific declarations are not listed in this record; they are typically included with the product or available from Schneider's documentation portal.