Schneider Electric GV2ME16K1U7 — Miniature Circuit Breakers (MCB)

Schneider GV2ME16K1U7 TeSys DOL Starter, 9-14 A, 230-240 VAC

MPNGV2ME16K1U7
Active

Schneider Electric TeSys GV2-ME DOL combination starter, GV2ME16K1U7, 9...14 A thermal protection, 230...240 V AC control, 3-pole.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

GV2ME16K1U7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter

Ratings

GV2ME16K1U7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity15 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 8 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 6 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3

Mechanical

GV2ME16K1U7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm

Other specifications

GV2ME16K1U7 — Other specifications
ParameterValue
Motor power5.5 kW at 400/415 V AC 50/60 Hz 5.5 kW at 440 V AC 50/60 Hz 7.5 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 3-pole contactor 1 combination block GV2AF01 1 motor circuit breaker type GV2ME
Motor starter typeNon reversing
Magnetic tripping current170 A
Coil voltage230/240 V AC 50/60 Hz
Thermal protection adjustment range9...14 A

Product details

The Schneider Electric GV2ME16K1U7 is a direct-on-line (DOL) combination motor starter from the TeSys GV2-ME range. It integrates a 3-pole motor circuit breaker and a contactor into one unit, with a thermal protection adjustment range of 9...14 A and a 230/240 V AC control circuit at 50/60 Hz. Rated for AC-3 utilisation category, it handles motor loads up to 5.5 kW at 400/415 V AC and 7.5 kW at 500 V AC. The magnetic tripping current is set at 170 A, providing short-circuit protection that coordinates with the contactor for Type 1 coordination.

Breaking capacity and fault protection

The GV2ME16K1U7 offers a breaking capacity of 15 kA at 400/415 V AC, 8 kA at 440 V AC, and 6 kA at 500 V AC, all conforming to IEC 60947-4-1.

The compact 45 mm width saves rail space compared to separate breaker-plus-contactor builds, and the fixed depth of 87 mm helps with enclosure depth planning.

Frequently asked questions

What is the thermal protection range and what does it mean for motor sizing?

The thermal protection adjustment range is 9...14 A. For a 400 V three-phase motor, this covers typical induction motors rated around 5.5 kW (full-load current roughly 11-12 A). Set the dial to match the motor nameplate FLA for overload protection.

What is the control circuit voltage requirement?

The control circuit (coil) is rated for 230/240 V AC at 50/60 Hz. Ensure your control transformer or supply matches this voltage — it is not a dual-voltage coil that also works at 110 V.

What breaking capacity does it offer at common industrial voltages?

At 400/415 V AC it breaks 15 kA; at 440 V AC it breaks 8 kA; at 500 V AC it breaks 6 kA — all per IEC 60947-4-1. This is the maximum prospective fault current the starter can safely interrupt at those voltages.

MPN