Schneider Electric GV2ME16K2B7 — Miniature Circuit Breakers (MCB)

Schneider TeSys GV2ME16K2B7 reversing starter, 9-14 A, 24 V

MPNGV2ME16K2B7
Obsolete

Schneider Electric TeSys GV2-ME reversing combination starter, GV2ME16K2B7, 9...14 A thermal protection range, 24 V AC 50/60 Hz control voltage.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

GV2ME16K2B7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter

Ratings

GV2ME16K2B7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity15 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 8 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 6 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3

Mechanical

GV2ME16K2B7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm

Other specifications

GV2ME16K2B7 — Other specifications
ParameterValue
Motor power5.5 kW at 400/415 V AC 50/60 Hz 5.5 kW at 440 V AC 50/60 Hz 7.5 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 combination block GV2AF01 1 motor circuit breaker type GV2ME 1 3-pole reversing contactor
Motor starter typeReversing
Magnetic tripping current170 A
Coil voltage24 V AC 50/60 Hz
Thermal protection adjustment range9...14 A

Product details

The GV2ME16K2B7 is a DOL reversing combination starter from the Schneider TeSys GV2-ME series. It integrates a motor-circuit breaker (thermal-magnetic protection, 9...14 A adjustment range) and a 3-pole reversing contactor into one block, plus the GV2AF01 combination base.

Rated for AC-3 utilization category — the standard for squirrel-cage motor switching. Motor power ratings: 5.5 kW at 400/415 V, 5.5 kW at 440 V, and 7.5 kW at 500 V (all 50/60 Hz). The magnetic trip is fixed at 170 A, which provides short-circuit protection coordinated to the thermal setting. Breaking capacity is 15 kA at 400/415 V (IEC 60947-4-1), dropping to 8 kA at 440 V and 6 kA at 500 V. Coordination is Type 1 — meaning the starter may need contact replacement after a fault, but the breaker clears the fault within its rating. This matters for panel selectivity studies.

Physical integration

Mounts on DIN rail. Dimensions: 45 mm wide, 152 mm tall, 87 mm deep. The 3-pole reversing contactor and breaker share the same footprint, saving panel width compared to separate components. The combination base GV2AF01 is included.

Frequently asked questions

What is the control voltage and thermal range?

Control circuit is 24 V AC 50/60 Hz. Thermal protection adjustment range is 9...14 A.

What motor power can this starter handle?

Rated for 5.5 kW at 400/415 V and 440 V, and 7.5 kW at 500 V, all 50/60 Hz, AC-3 duty.

What does Type 1 coordination mean here?

Under a fault within the breaking capacity, the starter may sustain damage requiring contact replacement, but the circuit breaker clears the fault safely without upstream device trip.

How do I source this obsolete part?

Through surplus or broker channels. Submit an RFQ for a quote; no lead-time or stock figures are available on this listing.