Skip to main content
Schneider Electric GV2ME16K2F7 — Molded Case Circuit Breakers (MCCB)

Schneider GV2ME16K2F7 TeSys reversing starter, 9-14 A, 110 V

MPNGV2ME16K2F7
Active

Schneider Electric TeSys GV2-ME reversing combination starter, GV2ME16K2F7, 9-14 A thermal protection, 110 V AC 50/60 Hz control voltage.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2ME16K2F7 — Identification
ParameterValue
Product / component typeMotor starter
GV2ME16K2F7 — Mechanical
ParameterValue
Height152 mm
Width45 mm
Depth87 mm
GV2ME16K2F7 — Electrical
ParameterValue
Breaking capacity15 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 8 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 6 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
GV2ME16K2F7 — Specifications
ParameterValue
Poles description3P
Device short nameGV2ME
GV2ME16K2F7 — Other specifications
ParameterValue
RangeTeSys
Motor power5.5 kW at 400/415 V AC 50/60 Hz 5.5 kW at 440 V AC 50/60 Hz 7.5 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device composition1 combination block GV2AF01 1 motor circuit breaker type GV2ME 1 3-pole reversing contactor
Motor starter typeReversing
Utilisation categoryAC-3
Magnetic tripping current170 A
Coil voltage110 V AC 50/60 Hz
Thermal protection adjustment range9...14 A

Product details

The GV2ME16K2F7 is a DOL reversing combination starter from the TeSys GV2-ME range. It's a single block that combines a motor circuit breaker (set for 9...14 A thermal protection) and a 3-pole reversing contactor with a 110 V AC 50/60 Hz coil. The built-in magnetic trip is set at 170 A, so it catches a locked-rotor fault fast. Rated for AC-3 duty (squirrel-cage motors), it handles up to 5.5 kW at 400/415 V, and can go to 7.5 kW at 500 V. The breaking capacity is 15 kA at 400/415 V per IEC 60947-4-1, which covers most industrial panel fault currents without needing an upstream fuse or breaker to do the heavy lifting. The GV2AF01 auxiliary contact block is included in the assembly, so you get a built-in signal contact for the PLC or status lamp without ordering extra parts.

The 9...14 A thermal adjustment range is what you set to match the motor's full-load amps. For a 5.5 kW motor at 400 V, you'd dial it in around 11-12 A. The 170 A magnetic trip is fixed — it's there for short-circuit protection, not overload, so you don't adjust it. That combination gives Type 1 coordination: under a fault, the starter might need contact replacement, but the downstream motor and upstream breaker stay intact. The reversing contactor pair means you get forward and reverse in one package, with mechanical interlocking built in. No risk of both contactors pulling in at once and shorting the phases. For a conveyor or hoist application, that's the difference between a controlled reversal and a bang.

Frequently asked questions

What's the closest alternative if GV2ME16K2F7 isn't available?

Within the same TeSys GV2-ME family, the direct alternative would be another reversing combination starter with the same 9-14 A thermal range and 110 V AC coil. The key difference between variants is the thermal adjustment range and coil voltage — the mechanical footprint and breaking capacity are shared across the GV2ME line. If you need a different coil voltage (e.g., 24 V DC or 230 V AC), you'd pick a different suffix on the same GV2ME16 base.

What compliance documentation does Schneider provide for this part?

As a current TeSys product, GV2ME16K2F7 carries IEC 60947-4-1 compliance for the breaking capacity ratings listed. Schneider typically provides a CE declaration of conformity, RoHS and REACH compliance statements, and a UL file number for the GV2ME series. The specific documentation pack is available from the distributor upon RFQ.

MPN