Skip to main content
Schneider Electric GV2ME16K2M7 — Miniature Circuit Breakers (MCB)

Schneider GV2ME16K2M7 TeSys reversing motor starter, 9…14 A,

MPNGV2ME16K2M7
Active

Schneider Electric TeSys GV2-ME, reversing DOL combination motor starter, GV2ME16K2M7, 9…14 A thermal adjustment, 220…230 VAC coil, 3-pole.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

GV2ME16K2M7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter

Ratings

GV2ME16K2M7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity15 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 8 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 6 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3

Mechanical

GV2ME16K2M7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm

Other specifications

GV2ME16K2M7 — Other specifications
ParameterValue
Motor power5.5 kW at 400/415 V AC 50/60 Hz 5.5 kW at 440 V AC 50/60 Hz 7.5 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 combination block GV2AF01 1 3-pole reversing contactor 1 motor circuit breaker type GV2ME
Motor starter typeReversing
Magnetic tripping current170 A
Coil voltage220/230 V AC 50/60 Hz
Thermal protection adjustment range9...14 A

Product details

The GV2ME16K2M7 is a reversing DOL combination motor starter from the Schneider TeSys GV2-ME family. It integrates a motor circuit breaker (type GV2ME), a 3-pole reversing contactor, and a combination block (GV2AF01) into one unit, so you wire a single device rather than assembling separate components for forward/reverse control of a three-phase motor. Thermal protection adjusts from 9 to 14 A, covering motors in the 5.5 kW range at 400/415 V AC (AC-3 duty). At 500 V it handles up to 7.5 kW. The magnetic trip is fixed at 170 A, clearing short-circuit faults fast without relying on upstream fuses for every fault.

That means the starter can safely interrupt a bolted fault up to 15 kA at the motor terminals — enough for most industrial panels fed from a typical 400 V distribution transformer. At 440 V the rating drops to 8 kA; at 500 V to 6 kA. Coordination is Type 1, so after a fault the starter may need contact replacement, but the upstream protection stays intact.

Panel fit and control voltage

Frequently asked questions

What are the key ratings for this reversing starter?

Thermal adjustment range 9…14 A, magnetic trip 170 A, breaking capacity 15 kA at 400/415 V AC (IEC 60947-4-1), motor power 5.5 kW at 400/415 V (AC-3), control voltage 220/230 V AC 50/60 Hz.

What is the physical size of the GV2ME16K2M7?

Width 45 mm, height 152 mm, depth 87 mm. Standard 45 mm DIN-rail module footprint.

What does the reversing starter include in one package?

It combines a GV2ME motor circuit breaker, a 3-pole reversing contactor, and a GV2AF01 combination block — all pre-assembled as a single reversing DOL starter.

MPN