Skip to main content
Schneider Electric GV2ME16K2Q7 — Molded Case Circuit Breakers (MCCB)

Schneider GV2ME16K2Q7 TeSys Reversing Starter, 9-14 A, 5.5 k

MPNGV2ME16K2Q7
Active

Schneider Electric TeSys GV2ME reversing motor starter, GV2ME16K2Q7, 9...14 A thermal protection, 380/400 V AC coil, 5.5 kW at 400 V, 15 kA breaking capacity.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2ME16K2Q7 — Identification
ParameterValue
Product / component typeMotor starter
GV2ME16K2Q7 — Mechanical
ParameterValue
Height152 mm
Width45 mm
Depth87 mm
GV2ME16K2Q7 — Electrical
ParameterValue
Breaking capacity15 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 8 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 6 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
GV2ME16K2Q7 — Specifications
ParameterValue
Poles description3P
Device short nameGV2ME
GV2ME16K2Q7 — Other specifications
ParameterValue
RangeTeSys
Motor power5.5 kW at 400/415 V AC 50/60 Hz 5.5 kW at 440 V AC 50/60 Hz 7.5 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device composition1 3-pole reversing contactor 1 combination block GV2AF01 1 motor circuit breaker type GV2ME
Motor starter typeReversing
Utilisation categoryAC-3
Magnetic tripping current170 A
Coil voltage380/400 V AC 50/60 Hz
Thermal protection adjustment range9...14 A

Product details

The Schneider GV2ME16K2Q7 is a TeSys GV2ME reversing DOL motor starter, combining a 3-pole reversing contactor, a GV2AF01 combination block, and a GV2ME motor circuit breaker in one unit. It's designed for AC-3 motor switching duty, with a thermal protection adjustment range of 9...14 A and a magnetic trip set at 170 A. Rated motor power reaches 5.5 kW at 400/415 V AC and 7.5 kW at 500 V AC, making it a direct fit for small-to-medium three-phase induction motors on pumps, conveyors, or compressors.

This starter carries a 15 kA breaking capacity at 400/415 V AC per IEC 60947-4-1, dropping to 8 kA at 440 V and 6 kA at 500 V. It's rated for Type 1 coordination, meaning after a fault the starter may need replacement but the upstream protection stays intact.

Panel integration

Depth is 87 mm, which clears most standard enclosure depths.

Frequently asked questions

What motor power can this starter handle?

It handles 5.5 kW at 400/415 V AC and 440 V AC, and 7.5 kW at 500 V AC, all at 50/60 Hz. The thermal adjustment range is 9...14 A, so it's sized for motors drawing that full-load current.

What is the breaking capacity at 400 V?

15 kA at 400/415 V AC per IEC 60947-4-1, with Type 1 coordination. At 440 V it drops to 8 kA, and at 500 V to 6 kA.

What is the control circuit voltage?

The coil is rated for 380/400 V AC at 50/60 Hz, so it's a line-voltage coil — no separate control transformer required if the panel supplies that voltage.

MPN
GV2ME16K2Q7