Schneider Electric GV2P10KD09G7
MPNGV2P10KD09G7
Obsolete
MOTOR STARTER 4A 120VAC|MOTOR STARTER 4A 120VAC
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Control type | Rotary knob |
| Motor starter type | Direct on-line contactor |
| Product or component type | Motor starter |
| Climatic withstand | IACS E10 |
| Voltage | 690 V AC 50/60 Hz IEC 60947-2 |
| [Ue] rated operational voltage | Power circuit Power circuit 10 MOhm for signalling circuit |
| [Uimp] rated impulse withstand voltage | 6 kV IEC 60947-2 |
| Breaking capacity | 100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 6 kA Icu 690 V AC 50/60 Hz IEC 60947-2 |
| Line rated current | 6.3 A |
| Magnetic tripping current | 78 A |
| [Ith] conventional free air thermal current | 6.3 A IEC 60947-4-1 |
| [Ics] rated service short-circuit breaking capacity | 100 % 690 V AC 50/60 Hz IEC 60947-2 100 % 500 V AC 50/60 Hz IEC 60947-2 100 % 230/240 V AC 50/60 Hz IEC 60947-2 100 % 440 V AC 50/60 Hz IEC 60947-2 100 % 400/415 V AC 50/60 Hz IEC 60947-2 |
All specifications
| Parameter | Value |
|---|---|
| Motor power | 2.2 kW 400/415 V AC 50/60 Hz 3 kW 500 V AC 50/60 Hz 4 kW 690 V AC 50/60 Hz |
| Motor power range | 0...0.5 kW 100...120 V 3 phase 0.55...1 kW 100...120 V 3 phase 0...0.5 kW 200...240 V 3 phase 0.55...1 kW 200...240 V 3 phase 1.1...2 kW 200...240 V 3 phase 0...0.5 kW 380...440 V 3 phase 0.55...1 kW 380...440 V 3 phase 1.1...2 kW 380...440 V 3 phase 2.2...3 kW 380...440 V 3 phase 4...6 kW 380...440 V 3 phase 0...0.5 kW 480...500 V 3 phase 0.55...1 kW 480...500 V 3 phase 1.1...2 kW 480...500 V 3 phase 2.2...3 kW 480...500 V 3 phase 4...6 kW 480...500 V 3 phase 0...0.5 kW 525...690 V 3 phase 0.55...1 kW 525...690 V 3 phase 1.1...2 kW 525...690 V 3 phase 2.2...3 kW 525...690 V 3 phase 4...6 kW 525...690 V 3 phase |
| Power dissipation per pole | 2.5 W |
| Power pole contact composition | 3 NO |
| Network frequency | 50/60 Hz IEC 60947-4-1 |
| Poles description | 3P |
| Rated duty | Continuous IEC 60947-4-1 |
| Utilisation category | AC-3 IEC 60947-4-1 Category A IEC 60947-2 |
| IK degree of protection | IK04 |
| IP degree of protection | IP20 IEC 60529 |
| Direct connector | Without |
| Connections - terminals | screw clamp terminals 2 0.002...0.009 in² (1...6 mm²) solid screw clamp terminals 2 0.002...0.009 in² (1.5...6 mm²) flexible without cable end screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) flexible with cable end |
| Pollution degree | 3 |
| Operating altitude | 6561.68 ft (2000 m) |
| Depth | 3.8 in (97 mm) |
| Width | 1.8 in (45 mm) |
| Height | 3.5 in (89 mm) |
| Electrical durability | 100000 cycles AC-3 440 V |
| Mechanical durability | 100000 cycles |
| Standards | IEC 60947-4-1 CSA C22.2 VDE 0113 VDE 0660 UL 508 IEC 60947-1 NF C 79-130 NF C 63-120 EN 60204 IEC 60947-2 NF C 63-650 |
| Range | TeSys |
| Category | US10I1122368 |
| Fixing mode | 35 mm symmetrical DIN rail clipped Panel screwed with 2 x M4 screws) |
| Fire resistance | 1562 °F (850 °C) IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Tightening torque | 15.05 lbf.in (1.7 N.m) screw clamp terminals |
| Operating position | Any position |
| Protective treatment | TH |
| Contact compatibility | M2 |
| Contactor application | Resistive load Motor control |
| Mechanical robustness | Vibrations contactor open2 Gn, 5...300 Hz Vibrations contactor closed4 Gn, 5...300 Hz Shocks contactor open10 Gn for 11 ms Shocks contactor closed15 Gn for 11 ms |
| Maximum operating rate | 25 cyc/h |
| Ambient air temperature for storage | -76...176 °F (-60...80 °C) |
| Ambient air temperature for operation | -4...140 °F (-20...60 °C) |
| Permissible ambient air temperature around the device | -40...158 °F (-40...70 °C) at Uc |
MPN