Skip to main content
Schneider Electric GV2P20AE11TQ

Schneider Electric GV2P20AE11TQ

MPNGV2P20AE11TQ
Obsolete

Motor circuit breaker, TeSys Deca, 3P, 13 to 18A, thermal magnetic, screw clamp terminals, with GVAE11, TQ 24 units

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2P20AE11TQ key specifications
ParameterValue
Control typeRotary handle
Network typeAC
Product or component typeMotor circuit breaker
Climatic withstandconforming to IACS E10
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2
Breaking capacity100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Current18 A
Magnetic tripping current341 A
[Ith] conventional free air thermal current18 A conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 75 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2

All specifications

GV2P20AE11TQ additional specifications
ParameterValue
Motor power7.5 kW at 400/415 V AC 50/60 Hz 9 kW at 500 V AC 50/60 Hz 15 kW at 690 V AC 50/60 Hz
Power dissipation per pole2.5 W
Network frequency50/60 Hz conforming to IEC 60947-2
Poles description3P
Phase failure sensitivityYes conforming to IEC 60947-4-1
Rated dutyUninterrupted conforming to IEC 60947-4-1
Utilisation categoryCategory A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1
IK degree of protectionIK04
IP degree of protectionIP20 conforming to IEC 60529
Mounting positionHorizontal Vertical
Connections - terminalsPower circuit: screw clamp terminal 2 cable(s) 1...6 mm² - solid Power circuit: screw clamp terminal 2 cable(s) 1.5...6 mm² - flexible without cable end Power circuit: screw clamp terminal 2 cable(s) 1...4 mm² - flexible with cable end
Operating altitude<= 2000 m
Depth97 mm
Width45 mm
ColorDark grey
Height89 mm
Electrical durability100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In
Mechanical durability100000 cycles
StandardsEN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2
RangeTeSys Deca
Fixing mode35 mm symmetrical DIN rail: clipped Panel: screwed (with 2 x M4 screws)
Fire resistance960 °C conforming to IEC 60695-2-11
Quantity per setSet of 24
Device short nameGV2P
Tightening torque1.7 N.m - on screw clamp terminal
Device applicationMotor protection
Trip unit technologyThermal-magnetic
Mechanical robustnessShocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz
Suitability for isolationYes conforming to IEC 60947-1
Auxiliary contact composition1 NO + 1 NC front
Ambient air temperature for storage-40...80 °C
Thermal protection adjustment range13...18 A conforming to IEC 60947-2
Ambient air temperature for operation-20...60 °C
MPN
GV2P20AE11TQ