The Schneider TeSys GV3A05 is an auxiliary contact block with three normally-open early-break contacts, designed for right-side mounting on GV3 manual motor starters in the TeSys Deca range. It's rated for 6 A conventional free-air thermal current (Ith) and carries a rated insulation voltage of 690 V per IEC 60947-1 or 600 V per UL 508 / CSA C22.2 No 14.
The early-break function means these NO contacts open ahead of the main power contacts when the starter trips, which matters for safety interlock circuits that need to drop out before the motor loses power. The AC-11 and DC-11 ratings tell you the switching capacity for inductive control loads: 850 VA at 380–415 V AC, 800 VA at 220–240 V AC, and 120 W at 220 V DC, all at 100,000 cycles. That 100,000-cycle mechanical durability figure is the expected life under rated conditions — not a guarantee, but a solid benchmark for panel lifecycle planning.
Mounts on the right side of a GV3 manual motor starter in the TeSys Deca line. No DIN-rail space consumed beyond the starter itself; the block clips on and adds about the width of the starter body.