Schneider Electric LC1F5002 — Contactors

Schneider Electric LC1F5002 TeSys F Contactor, 700 A AC-1

MPNLC1F5002
Obsolete

Schneider Electric TeSys F LC1F5002 contactor, 2-pole, 700 A AC-1 rated operational current at ≤440 V, 48-1000 V AC coil, plate mounting, 9.1 x 9.2 x 9.4 in.

$1,620.52Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC1F5002 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load
LC1F5002 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 460 V DC
Utilisation categoryAC-1
LC1F5002 — Contacts & Poles
ParameterValue
Pole configuration2P
LC1F5002 — Environmental
ParameterValue
IP degree of protectionIP20 front face with shrouds IEC 60529 IP20 front face with shrouds VDE 0106
Operating altitude9842.52 ft (3000 m) without derating
Mechanical robustnessVibrations contactor open2 Gn, 5...300 Hz Vibrations contactor closed4 Gn, 5...300 Hz Shocks contactor open9 Gn for 1/2 sine wave (11 ms) Shocks contactor closed15 Gn for 1/2 sine wave (11 ms)
Protective treatment / pollution degreeTH
LC1F5002 — Approvals
ParameterValue
StandardsJIS C8201-4-1 EN 60947-1 IEC 60947-1 EN 60947-4-1 IEC 60947-4-1
LC1F5002 — Mechanical
ParameterValue
Width9.2 in (233 mm)
Height9.4 in (238 mm)
Depth9.1 in (232 mm)

Product details

700 A resistive-load contactor — what the ratings mean for fit

The LC1F5002 is a 2-pole TeSys F contactor rated 700 A in AC-1 utilisation category at ≤440 V, 40 °C. AC-1 covers resistive loads — heaters, ovens, lighting banks — where the switching current equals the steady-state current. This is not a motor-starting contactor; the AC-3 rating would be lower. The contactor carries 2 NO power poles. The control circuit accepts 48-1000 V AC 40-400 Hz with LX1/LX9 coil options, or 48-440 V DC with LX4 coil. Inrush power is 1050-1150 VA AC; hold-in drops to 16-20 VA.

Lifecycle status — EOL hot, plan the replacement

Mechanical durability is rated 10 Mcycles. Maximum operating rate is 2400 cycles/hour at 55 °C. Heat dissipation is 18 W total, 88 W per pole in AC-1 duty.

Standards compliance and mounting

The LC1F5002 is certified to IEC 60947-1, IEC 60947-4-1, EN 60947-1, EN 60947-4-1, and JIS C8201-4-1. Rated insulation voltage is 1000 V per IEC 60947-4-1, 1500 V per VDE 0110 group C. Overvoltage category III. IP20 front face with shrouds per IEC 60529 and VDE 0106. Mounting is plate-mount — not DIN rail. Dimensions: depth 9.1 in (232 mm), width 9.2 in (233 mm), height 9.4 in (238 mm). Power circuit terminals accept ring lugs up to 240 mm² or bar 40 x 5 mm, bolted connection. Tightening torque: power circuit 35 N·m, control circuit 1.2 N·m. Associated fuse rating: 500 A aM or 800 A gG at ≤440 V. Rated breaking capacity 4000 A per IEC 60947-4-1; rated making capacity 5000 A AC. Operating altitude up to 3000 m without derating.

MPN
LC1F5002