Specifications

LC1E06004Q7IN — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load
LC1E06004Q7IN — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-1
LC1E06004Q7IN — Contacts & Poles
ParameterValue
Pole configuration4P
LC1E06004Q7IN — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E06004Q7IN — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5
LC1E06004Q7IN — Mechanical
ParameterValue
Width45 mm
Height74 mm
Depth80 mm

Product details

The Schneider Electric LC1E06004Q7IN is a 4-pole (4NO) contactor from the Easy TeSys Control range, rated for AC-1 resistive loads at 20 A up to 415 V, with a 380 V coil. It is designed for switching resistive heating elements, lighting banks, or other non-inductive loads where inrush current is minimal — the AC-1 utilisation category tells you this is not a motor-starting contactor. The 4-pole configuration gives you four normally-open power contacts in a 45 mm wide package that mounts on DIN rail or a plate.

The AC-1 rating of 20 A at ≤415 V defines the continuous resistive current each pole can carry. For a procurement decision, this means the contactor is sized for loads like electric heaters or incandescent lighting — not for motors, transformers, or capacitor banks that draw a high inrush. The 380 V coil (part of the order code suffix) operates within the -20 to 70 °C ambient range at rated voltage, with a guaranteed non-overlap time of 1.5 ms between NC and NO contacts on both energisation and de-energisation, which prevents shoot-through in interlocking circuits. The contactor carries IP2X finger protection per IEC 60529, meaning it is safe for panel mounting where operators may reach near the terminals.

Integration into a panel

The contactor measures 45 mm wide by 74 mm high by 80 mm deep, fitting a standard DIN-rail footprint or direct plate mounting. The 4-pole block occupies one modular width, so a multi-contactor panel can be laid out in a single row. Operating altitude is rated to 3000 m without derating — relevant if the panel goes into a high-altitude installation like a mine or mountain facility. Storage temperature extends from -60 to 80 °C, which covers most warehouse and shipping conditions.

Frequently asked questions

What is the closest alternative to the LC1E06004Q7IN?

No direct order-code successor is listed in the available records. A parametric replacement from the same Easy TeSys Control range with 4 poles, AC-1 rating at 20 A or higher, and a 380 V coil would match the footprint and function. Contact us with your application details for a qualified cross-reference.

What compliance standards does this contactor meet?

It is certified to EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and the equivalent GB/T 14048.1, 14048.4, and 14048.5 standards. Fire resistance is rated at 850 °C per IEC 60695-2-1. The protective treatment meets pollution degree 3 per IEC 60068.

What are the mounting options for this contactor?

It mounts on a DIN rail or directly to a plate. The 45 mm width fits standard modular panel layouts.