Skip to main content
Schneider Electric LC1E0601M6 — Contactors

Schneider Electric LC1E0601M6 Easy TeSys Contactor, 6A AC-3,

MPNLC1E0601M6
Obsolete

Schneider Electric Easy TeSys Control LC1E0601M6, 3P contactor, AC-3/AC-3e 6A ≤440V, 220V AC 60Hz coil, 1NC auxiliary, obsolete.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC1E0601M6 — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationMotor control Resistive load
LC1E0601M6 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-3 AC-3e AC-1
LC1E0601M6 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1E0601M6 — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068-2-30
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E0601M6 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ
LC1E0601M6 — Mechanical
ParameterValue
Width45 mm
Height74 mm
Depth80 mm

Product details

It switches 6 A in AC-3 duty (≤440 V) and carries AC-1 and AC-3e utilisation categories as well. The coil is 220 V AC at 60 Hz, and it includes one normally-closed auxiliary contact. Mounts on a plate or DIN rail, with an IP2X finger-safe enclosure. The 45 mm width and 74 mm height fit standard panel layouts; depth is 80 mm. Compliant with EN/IEC 60947-1, -4-1, -5-1 and GB/T equivalents, plus EN/IEC 60335-1 Clause 30.2 and -2-40 Annex JJ for appliance applications. Fire resistance tested to 850 °C per IEC 60695-2-1.

No official successor order code is listed in the lifecycle record. For a replacement, the buyer should compare the Easy TeSys Control range's current active contactors by coil voltage, pole count, and AC-3 rating.

AC-3e extends that to energy-efficient motors with higher inrush. AC-1 covers resistive loads at the same current level. The 1.5 ms non-overlap time between NC and NO contacts ensures that the auxiliary circuit transitions cleanly without momentary bridging — important for safety interlocks or logic sequences.

Frequently asked questions

What replaces the LC1E0601M6?

No official successor order code is provided. For a replacement, compare active contactors in the Easy TeSys Control range with the same coil voltage (220 V AC 60 Hz), pole count (3P), and AC-3 current (6 A).

What are the key ratings of the LC1E0601M6?

3-pole contactor, AC-3/AC-3e 6 A at ≤440 V, AC-1 same current. Coil 220 V AC 60 Hz. One NC auxiliary contact. Mounts on plate or DIN rail, 45 mm wide, 80 mm deep.

What compliance standards does the LC1E0601M6 meet?

It complies with EN/IEC 60947-1, -4-1, -5-1, GB/T 14048.1.4.5, and EN/IEC 60335-1 Clause 30.2 and -2-40 Annex JJ. Fire resistance tested to 850 °C per IEC 60695-2-1.

MPN
LC1E0601M6