Skip to main content
Schneider Electric LC1E0601N5 — Contactors

Schneider Electric LC1E0601N5 Easy TeSys Contactor, 6A AC-3,

MPNLC1E0601N5
Active

Schneider Electric Easy TeSys Control, LC1E0601N5, 3P contactor, AC-3/AC-3e 6A ≤440V, 415V AC 50Hz coil, 1NC auxiliary.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LC1E0601N5 — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationMotor control Resistive load
LC1E0601N5 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-3 AC-3e AC-1
LC1E0601N5 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1E0601N5 — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068-2-30
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E0601N5 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ
LC1E0601N5 — Mechanical
ParameterValue
Width45 mm
Height74 mm
Depth80 mm

Product details

The Schneider Electric LC1E0601N5 is a 3-pole contactor from the Easy TeSys Control range, rated 6 A in AC-3 and AC-3e utilisation categories at up to 440 V. The AC-3 rating means it handles starting and stopping of squirrel-cage motors — the inrush during start is the real stress, and this contactor is sized for that duty cycle. The AC-1 rating covers resistive loads like heaters, where the current stays steady. The 415 V AC 50 Hz coil is built for European-standard control circuits; verify your control voltage matches before wiring. It carries a 1 NC auxiliary contact, which is the minimum for a holding circuit or a status feedback to a PLC input.

Standards and compliance — what the approvals tell you

This contactor is certified to EN/IEC 60947-4-1 (the main standard for contactors and motor-starters), plus EN/IEC 60947-1 (general rules) and EN/IEC 60947-5-1 (control-circuit devices). It also meets the Chinese GB/T equivalents and the glow-wire test requirements of EN/IEC 60335-1 Clause 30.2 for household appliances.

The IP2X finger protection means the live parts are shielded from accidental contact once installed in an enclosure.

Frequently asked questions

What utilisation categories does this contactor cover?

It is rated for AC-3 and AC-3e (motor starting and running) and AC-1 (resistive loads). The AC-3 rating at 6 A up to 440 V is the key spec for motor control applications.

What standards does the LC1E0601N5 comply with?

It complies with EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and the Chinese GB/T 14048 series. It also meets the glow-wire requirements of EN/IEC 60335-1 Clause 30.2 and EN/IEC 60335-2-40 Annex JJ.

How is the LC1E0601N5 mounted?

It mounts on a DIN rail or directly to a mounting plate. The 45 mm width fits standard DIN-rail enclosures.

MPN
LC1E0601N5