It carries a 6 A rating in AC-3 utilisation category at ≤440 V, with a 240 V AC 50 Hz coil and one normally-closed auxiliary contact. Rated for AC-3 (motor starting), AC-3e (enhanced motor), and AC-1 (resistive) duty, it handles the inrush of induction motors up to its rated current and switches resistive loads cleanly. The 1.5 ms non-overlap time between NC and NO contacts ensures break-before-make in reversing or star-delta circuits.
IP2X finger protection per IEC 60529 covers the live parts once installed; the TH protective treatment (pollution degree 3) per IEC 60068-2-30 means it withstands humid, mildly corrosive environments typical of industrial control panels.