Its headline rating is 6 A in AC-3 utilisation category at ≤440 V — that's the motor-switching current, not the resistive load rating. The 48 V AC coil pulls in reliably at nominal voltage; the non-overlap time of 1.5 ms on both energisation and de-energisation ensures the NC and NO contacts never make simultaneously, which matters when you're interlocking a reversing starter or bypass circuit.
IP2X means finger-safe from the front but not sealed; keep it inside an enclosure, not in a washdown zone.
This part is obsolete per the manufacturer. That means no factory orders, no scheduled production. Sourcing is through surplus and broker channels — we can quote against an RFQ for what's available on the open market. No official successor is listed, so a direct drop-in replacement isn't guaranteed; verify fit against your existing panel layout and wiring.
Protective treatment TH (pollution degree 3) means it handles humid, mildly corrosive environments — typical for industrial control panels not in direct weather.