Skip to main content
Schneider Electric LC1E0610R5 — Contactors

Schneider Electric LC1E0610R5 Easy TeSys Contactor, 6A AC-3,

MPNLC1E0610R5
Obsolete

Schneider Electric Easy TeSys Control LC1E, LC1E0610R5, 3P(3NO) contactor, AC-3/AC-3e ≤440V 6A, 440V AC 50Hz coil, 1NO auxiliary contact.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1E0610R5 — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationMotor control Resistive load
LC1E0610R5 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-3 AC-3e AC-1
LC1E0610R5 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1E0610R5 — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068-2-30
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E0610R5 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ
LC1E0610R5 — Mechanical
ParameterValue
Width45 mm
Height74 mm
Depth80 mm

Product details

Product Overview & Key Ratings

The Schneider Electric LC1E0610R5 is a 3-pole contactor from the Easy TeSys Control range, rated for AC-3 and AC-3e utilisation categories at 6 A up to 440 V, with a 440 V AC 50 Hz coil and one normally-open auxiliary contact. The AC-3 rating means it's designed for starting and stopping squirrel-cage motors under load — the 6 A figure governs the motor full-load current it can handle, not the resistive heating current. It also carries an AC-1 rating for resistive loads, so it can switch heater banks or lighting banks at a higher current than the AC-3 motor rating. The 1.5 ms non-overlap time between NC and NO contacts on both energisation and de-energisation ensures break-before-make operation in safety-related control circuits.

Mounting & Integration

The IP2X degree of protection means it's touch-safe against fingers but not sealed against dust or moisture — suitable for enclosed panel installation, not washdown environments.

No official successor order code is listed in the manufacturer's lifecycle data. A parametric cross-reference to a current Easy TeSys or TeSys Deca contactor with matching coil voltage and pole configuration would be needed for a replacement — verify the mounting footprint and auxiliary contact arrangement before substituting.

Compliant with EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and the corresponding GB/T standards. Also meets EN/IEC 60335-1 Clause 30.2 and EN/IEC 60335-2-40 Annex JJ for fire resistance, with a glow-wire test at 850 °C per IEC 60695-2-1.

Frequently asked questions

What are the key ratings of the LC1E0610R5?

It is a 3-pole contactor rated 6 A in AC-3/AC-3e at up to 440 V, with a 440 V AC 50 Hz coil and one normally-open auxiliary contact. It also carries an AC-1 resistive load rating.

What standards does the LC1E0610R5 comply with?

It complies with EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and the corresponding GB/T standards, plus EN/IEC 60335-1 Clause 30.2 and EN/IEC 60335-2-40 Annex JJ for fire resistance.

How do I source the LC1E0610R5 if it's obsolete?

Since it is obsolete, sourcing is through surplus or independent channels. Submit an RFQ for a quote on available stock — no factory lead time or guaranteed supply exists.

MPN