It is rated for AC-1 utilisation category at 25 A, with a rated operational voltage up to 415 V and a 48 V coil. The contactor is designed for resistive load switching in control panels.
The 4-pole configuration with 2 normally-open and 2 normally-closed contacts gives flexibility for switching multiple circuits or implementing interlocking. The non-overlap time of 1.5 ms on both energisation and de-energisation between NC and NO contacts is a safety feature that prevents momentary short-circuits when switching between contact sets — critical for applications like reversing starters or bypass circuits. IP2X protection means it is finger-safe but not sealed against dust or moisture; install inside an enclosure for washdown environments. Operates in ambient temperatures from -5 °C to 55 °C, with storage range of -60 °C to 80 °C. The TH protective treatment (pollution degree 3) per IEC 60068 means it withstands humid, mildly corrosive atmospheres typical of industrial panels.
Fire resistance tested to 850 °C per IEC 60695-2-1. Mechanical robustness rated for vibrations up to 3 Gn (contacts closed) and shocks up to 10 Gn (contacts closed).