Skip to main content
Schneider Electric LC1E09008N5WBSIN — Contactors

Schneider Electric LC1E09008N5WBSIN Easy TeSys Contactor, 25

MPNLC1E09008N5WBSIN
Active

Schneider Electric Easy TeSys Control, contactor LC1E09008N5WBSIN, 4P, 25 A AC-1, coil 415 V AC 50 Hz, screw clamp terminals, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1E09008N5WBSIN — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load
LC1E09008N5WBSIN — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: <= 690 V AC 50/60 Hz
Utilisation categoryAC-1
LC1E09008N5WBSIN — Contacts & Poles
ParameterValue
Pole configuration4P
LC1E09008N5WBSIN — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
Operating altitude3000 m
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)
Protective treatment / pollution degreeTH conforming to IEC 60068
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E09008N5WBSIN — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5
LC1E09008N5WBSIN — Mechanical
ParameterValue
Width45 mm
Height74 mm
Depth80 mm

Product details

The Schneider Electric LC1E09008N5WBSIN is a 4-pole contactor from the Easy TeSys Control range, rated 25 A in AC-1 utilisation category for resistive loads at up to 415 V AC. That AC-1 rating means it's sized for heater banks, lighting, or other non-inductive circuits — not motor starting, where the AC-3 duty class would apply.

Rated insulation voltage (Ui) is 690 V per IEC 60947-4-1, giving headroom for 400 V line-to-line systems. The rated breaking capacity is 72 A at 440 V, and the making capacity is 90 A at 440 V AC — both conforming to IEC 60947. That means it can close into and interrupt fault currents well above its continuous rating, which matters for coordination with upstream protection. The IP20 finger-safe terminals are standard for enclosure-mounted gear — no additional shrouding needed inside a closed panel. Mounts on DIN rail or plate. Screw-clamp terminals accept up to 6 mm² solid or 4 mm² flexible with ferrule on the power side. Tightening torque is 1.2 N.m for both power and control circuits — a common value that your existing torque driver handles without a change.

Protective treatment TH per IEC 60068 means it's tested for tropical/humid environments. No UL or CSA mark is listed in the spec record, so if your panel requires those, check the nameplate or request a variant.

Frequently asked questions

What is the rated operational current for this contactor?

25 A at ≤40 °C, ≤415 V AC, AC-1 utilisation category (resistive load).

What control voltage does the coil require?

415 V AC at 50 Hz. Drop-out occurs between 0.3 and 0.6 Uc; pick-up requires 0.7 to 1.25 Uc.

What compliance documentation is available?

The contactor is certified to EN/IEC 60947-1, -4-1, -5-1 and GB/T equivalents. Protective treatment TH per IEC 60068. Fire resistance 850 °C per IEC 60695-2-1.

MPN