The Schneider Electric LC1E09008N7IN is a 4-pole contactor from the Easy TeSys Control range, configured 2NO+2NC, rated for AC-1 resistive load switching at 25 A up to 415 V. It is designed for resistive load applications — think heater banks or lighting circuits — not motor starting. The AC-1 utilisation category tells you the contacts are rated for the lower inrush of resistive loads, not the high locked-rotor current of a motor.
Mounts on DIN rail or a plate — the 45 mm wide footprint fits standard panel cutouts alongside other Easy TeSys components. The contactor includes a guaranteed non-overlap time of 1.5 ms between NC and NO contacts on both energisation and de-energisation, which prevents momentary short-circuits in interlocking circuits. Rated for operation up to 3000 m altitude and -20 to 70 °C ambient at coil voltage, with storage down to -60 °C. The TH protective treatment (pollution degree 3) means it handles the damp, mildly corrosive conditions typical of industrial control panels.
We can quote to order against an RFQ from our multi-source network, but expect last-time-buy dynamics on availability. No official successor order code is listed in the lifecycle record. If you need a drop-in replacement, a cross-reference to a current Easy TeSys or TeSys Deca contactor with the same coil voltage and pole configuration will require a parametric check — the 45 mm width and DIN-rail mounting are standard, but verify the control circuit ratings match.