It's rated for AC-1 resistive loads up to 25 A at ≤415 V, with a 240 V coil. This puts it in the panel for switching heater banks, lighting, or other non-inductive loads where the AC-1 duty class applies — the contactor's thermal current rating governs, not the motor-breaking AC-3 curve.
Mounting and integration notes
The IP2X finger-safe front cover meets IEC 60529, which is standard for enclosed panel gear — no special shrouding needed inside a locked cabinet. The non-overlap time between NC and NO contacts is guaranteed at 1.5 ms on both energisation and de-energisation, which matters if you're using the NC leg for a safety interlock that must break before the NO power leg closes.
Rated for operation from -5 °C to 55 °C ambient, with storage from -60 °C to 80 °C. Fire resistance tested to 850 °C per IEC 60695-2-1.