Skip to main content
Schneider Electric LC1E0910B6 — Contactors

Schneider LC1E0910B6 Easy TeSys Contactor, 9A AC-3, 24V AC C

MPNLC1E0910B6
Obsolete

Schneider Electric Easy TeSys Control LC1E0910B6, obsolete 3-pole contactor, 9 A AC-3/AC-3e at ≤440 V, 24 V AC 60 Hz coil, 1 NO auxiliary contact, plate/DIN-rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1E0910B6 — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationMotor control Resistive load
LC1E0910B6 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-3 AC-3e AC-1
LC1E0910B6 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1E0910B6 — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068-2-30
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E0910B6 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ
LC1E0910B6 — Mechanical
ParameterValue
Width45 mm
Height74 mm
Depth80 mm

Product details

The Schneider Electric LC1E0910B6 is a 3-pole contactor from the Easy TeSys Control range, rated for 9 A in AC-3 and AC-3e utilisation categories at up to 440 V, with a 24 V AC 60 Hz coil and one normally open auxiliary contact. It's built for motor control and resistive load switching in control panels, mounting to either a plate or a DIN rail.

The 9 A AC-3 rating is the motor-switching current at 440 V — the figure that decides whether this contactor handles your motor load. AC-3 covers starting and stopping of squirrel-cage motors, where the contacts close on inrush and break the running current. The same contactor also carries an AC-1 rating for resistive loads, so it can switch heaters or lighting banks at a higher current (the exact AC-1 value is not listed here, but the utilisation category is confirmed). The 24 V AC coil at 60 Hz is a fixed-frequency coil — if your panel runs 50 Hz, the coil impedance changes and the pickup/dropout voltages shift. The part is specified for 60 Hz only, so verify coil compatibility before dropping it into a 50 Hz circuit. The non-overlap time of 1.5 ms on both energisation and de-energisation, guaranteed between NC and NO contacts, means the contactor breaks before make — critical for interlocking circuits where you cannot allow momentary shorting across power legs. Mounting is straightforward: 45 mm width on a DIN rail or plate, with an operating altitude of 3000 m without derating. The IP2X finger protection means it's safe for open-panel mounting where accidental contact is possible, but not for washdown environments.

Lifecycle Reality — This Part Is Obsolete

The LC1E0910B6 is marked obsolete by Schneider Electric. There is no official successor order code listed in the available records, so a direct drop-in replacement from the same brand is not confirmed.

The contactor carries compliance with EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and the corresponding GB/T standards for the Chinese market. It also meets EN/IEC 60335-1 Clause 30.2 and EN/IEC 60335-2-40 Annex JJ for appliance applications. Fire resistance is tested to 850 °C per IEC 60695-2-1. Protective treatment is TH (pollution degree 3) per IEC 60068-2-30, suitable for humid environments.

Frequently asked questions

What are the key dimensions for panel layout?

The LC1E0910B6 measures 45 mm wide, 74 mm high, and 80 mm deep. It mounts on a DIN rail or directly to a plate.

What compliance documentation does Schneider provide for this part?

The contactor is certified to EN/IEC 60947-1, -4-1, -5-1, and the corresponding GB/T standards. It also meets EN/IEC 60335-1 Clause 30.2 and EN/IEC 60335-2-40 Annex JJ for appliance use. Fire resistance is rated at 850 °C per IEC 60695-2-1, and protective treatment is TH (pollution degree 3) per IEC 60068-2-30.

MPN