The LC1E0910M6 is a 3-pole contactor from Schneider Electric's Easy TeSys Control range, rated 9 A in AC-3 and AC-3e utilisation categories at ≤440 V — the standard motor-switching duty for squirrel-cage induction motors up to that current. The 220 V AC 60 Hz coil pulls in the armature; a single normally-open auxiliary contact is built in for feedback or interlock wiring.
Standards and environmental rating
The -5 to 55 °C operational band is the one that governs continuous duty inside a closed panel; above that, derate or forced ventilation applies. Altitude derating starts above 3000 m — irrelevant for most installations. This is a current-catalog part, not a phase-out or NRND line — no last-time-buy clock ticking.
Coil and auxiliary contact details
The 220 V AC 60 Hz coil is a fixed-frequency variant — verify your control supply is 60 Hz, not 50 Hz, or the hold-in force and dropout margin shift.