Skip to main content
Schneider Electric LC1E12004N5WBIN — Contactors

Schneider Electric LC1E12004N5WBIN Easy TeSys Contactor, 32

MPNLC1E12004N5WBIN
Obsolete

Schneider Electric Easy TeSys Control LC1E12004N5WBIN, 4-pole contactor, 32 A AC-1 at ≤415 V AC, 415 V AC 50 Hz coil, screw clamp terminals, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1E12004N5WBIN — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load
LC1E12004N5WBIN — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: <= 690 V AC 50/60 Hz
Utilisation categoryAC-1
LC1E12004N5WBIN — Contacts & Poles
ParameterValue
Pole configuration4P
LC1E12004N5WBIN — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
Operating altitude3000 m
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)
Protective treatment / pollution degreeTH conforming to IEC 60068
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E12004N5WBIN — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5
LC1E12004N5WBIN — Mechanical
ParameterValue
Width45 mm
Height74 mm
Depth80 mm

Product details

The Schneider Electric LC1E12004N5WBIN is a 4-pole contactor from the Easy TeSys Control range, rated for 32 A in AC-1 utilisation category (resistive load) at up to 415 V AC. The coil is 415 V AC 50 Hz wide-range, drawing 95 VA inrush at 50 Hz. It switches resistive loads — heaters, lighting banks, non-inductive elements — where the AC-1 rating governs the continuous current-carrying capacity, not the motor inrush that an AC-3 rating would cover.

Mechanical durability is 10 million cycles; electrical durability is 300,000 cycles at AC-1. That means in a resistive switching application with moderate duty (say, cycling a heater bank a few times per hour), the contactor will outlast most panel builds. The maximum operating rate is 1800 cycles per hour at 60 °C — fast enough for cyclic process control. The control circuit voltage limits are 0.7 to 1.25 Uc for pickup and 0.3 to 0.6 Uc for dropout at 50 Hz.

Mounts on DIN rail or plate (screw-clamp terminals). Dimensions are 45 mm wide, 74 mm high, 80 mm deep — a compact 4-pole footprint that fits standard 45 mm-wide DIN-rail slots. IP20 protection means it is suitable for enclosed panels only, not washdown or outdoor locations. Pollution degree 3 (conductive pollution) is typical for industrial control panels. Terminals accept up to 6 mm² solid or 4 mm² flexible with ferrule on the power side; control circuit terminals accept up to 6 mm² solid. Tightening torque is 1.2 N.m for both power and control circuits — consistent with standard screw-clamp contactors in this frame size.

Fire resistance is 850 °C per IEC 60695-2-1. Protective treatment is TH (tropical heat) per IEC 60068. Operating altitude is 3000 m. Overvoltage category III.

Frequently asked questions

What is the depth of LC1E12004N5WBIN?

80 mm.

What range does LC1E12004N5WBIN belong to?

Easy TeSys Control (also listed as Easy TeSys).