Skip to main content
Schneider Electric LC1E12004N7IN — Contactors

Schneider Electric LC1E12004N7IN Easy TeSys Contactor, 4P, 3

MPNLC1E12004N7IN
Obsolete

Schneider Electric Easy TeSys Control contactor, LC1E12004N7IN, 4P (4NO), AC-1 utilisation, 32 A at ≤415 V, 45 x 74 x 80 mm.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1E12004N7IN — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load
LC1E12004N7IN — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-1
LC1E12004N7IN — Contacts & Poles
ParameterValue
Pole configuration4P
LC1E12004N7IN — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E12004N7IN — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5
LC1E12004N7IN — Mechanical
ParameterValue
Width45 mm
Height74 mm
Depth80 mm

Product details

Compliance and lifecycle status

The LC1E12004N7IN is classified as Obsolete per the manufacturer's lifecycle record. For a BOM line requiring this exact order code, sourcing is through the surplus or broker channel; we can quote against an RFQ.

This is a 4-pole contactor (4 normally-open poles) from the Easy TeSys Control range, rated for AC-1 utilisation category at 32 A on a power circuit up to 415 V. AC-1 covers resistive loads — heating elements, lighting banks, or non-inductive loads — not motor starting. For motor duty (AC-3), you would need a different coil or a higher-rated frame. Depth of 80 mm must be checked against enclosure gland-plate clearance.

Mechanical and environmental robustness

Rated for vibration at 1.5 Gn (contacts open) and 3 Gn (contacts closed) over 5–300 Hz, and shock at 7 Gn (open) and 10 Gn (closed) for 11 ms. This makes it viable on mobile equipment or near rotating machinery, though the IP2X enclosure limits placement to a protected panel. Maximum operating altitude is 3000 m — above that, dielectric withstand and thermal dissipation derate.

Frequently asked questions

What compliance documentation does this contactor carry?

It is certified to EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and the corresponding GB/T standards. Fire resistance is verified to 850 °C per IEC 60695-2-1. Protective treatment meets TH (pollution degree 3) per IEC 60068.

What is the physical size of this contactor?

Width 45 mm, height 74 mm, depth 80 mm. It mounts on a DIN rail or plate.

What load type is this contactor rated for?

AC-1 utilisation category, meaning resistive loads only — heaters, lighting, non-inductive circuits. Rated 32 A at up to 415 V. Not suitable for motor starting (AC-3 duty).

MPN