It is rated for AC-1 utilisation category at 32 A on a supply up to 415 V, with a 230 V coil — meaning it is built for resistive load switching, not motor starting. The AC-1 rating covers heating elements, lighting banks, and other non-inductive loads where inrush is minimal.
The contactor carries compliance with EN/IEC 60947-1, EN/IEC 60947-4-1, and EN/IEC 60947-5-1, plus the Chinese GB/T equivalents — covering the main low-voltage switchgear and controlgear standards for contactors. Fire resistance is tested to 850 °C per IEC 60695-2-1. The enclosure is rated IP2X per IEC 60529, meaning it is finger-safe but not sealed against dust or moisture. Protective treatment is TH (pollution degree 3) per IEC 60068, so it tolerates the conductive pollution typical in industrial panels.
Mounts on a plate or DIN rail. The non-overlap time between NC and NO contacts is guaranteed at 1.5 ms on both energisation and de-energisation — important for interlocking circuits where you need to avoid a momentary short across poles during transition.