Schneider Electric LC1E1201F7 — Contactors

Schneider LC1E1201F7 Easy TeSys Contactor, 12A AC-3, 110V AC

MPNLC1E1201F7
Active

Schneider Electric Easy TeSys Control LC1E1201F7, 3-pole contactor, 12 A AC-3/AC-3e at ≤440 V, 110 V AC coil 50/60 Hz, 1 NC auxiliary contact.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC1E1201F7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationMotor control Resistive load

Ratings & Performance

LC1E1201F7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-3 AC-3e AC-1

Contacts & Poles

LC1E1201F7 — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

LC1E1201F7 — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068-2-30
Fire resistance850 °C conforming to IEC 60695-2-1

Approvals

LC1E1201F7 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ

Mechanical

LC1E1201F7 — Mechanical
ParameterValue
Width45 mm
Height74 mm
Depth80 mm

Product details

It carries a 12 A rating in AC-3 and AC-3e utilisation categories at ≤440 V, which means it is sized for switching three-phase induction motors up to that current — the AC-3 category specifically covers starting and stopping squirrel-cage motors under full load. The 110 V AC coil operates on 50/60 Hz supplies, a common control voltage in industrial panels worldwide. This timing is critical when the contactor is used in safety circuits or reversing starters where a break-before-make sequence must be enforced to prevent phase-to-phase shorts.

Standards, approvals, and environmental tolerance

Protective treatment TH conforming to IEC 60068-2-30 means it is tested for damp heat, cyclic — suitable for non-condensing humid environments typical of many industrial sites.

IP2X finger protection per IEC 60529 covers the front of the device — adequate for enclosed panels where accidental contact is prevented by the enclosure door. Mechanical robustness is specified for vibration: 1.5 Gn (5–300 Hz) with contacts open, 3 Gn with contacts closed. Shock resistance is 7 Gn for 11 ms open, 10 Gn for 11 ms closed. These figures confirm the contactor holds its state under moderate machine vibration — relevant when mounted on a panel attached to a running conveyor or compressor skid.

Frequently asked questions

What utilisation categories does this contactor support?

It is rated for AC-3 (squirrel-cage motor starting/stopping), AC-3e (enhanced AC-3 for energy-efficient motors), and AC-1 (resistive loads). The AC-3/AC-3e rating at 12 A and ≤440 V is the primary motor-switching spec; AC-1 carries a higher current rating for resistive loads like heaters.

What is the coil voltage and frequency?

The coil is 110 V AC, 50/60 Hz. This is a common control voltage in North American and many international panels. Ensure the control transformer or supply matches this voltage; the contactor will not pull in reliably below about 85% of rated voltage.

Does this contactor include an auxiliary contact block?

It comes with one built-in normally-closed (NC) auxiliary contact. The non-overlap time between NC and NO contacts is guaranteed at 1.5 ms on both energisation and de-energisation, which is important for interlocking in reversing or safety circuits.

What compliance documentation is available for the LC1E1201F7?

The contactor is certified to EN/IEC 60947-1, 60947-4-1, and 60947-5-1, plus GB/T 14048.1/4/5 for China. It also meets EN/IEC 60335-1 Clause 30.2 and EN/IEC 60335-2-40 Annex JJ for household/HVAC appliance safety. Fire resistance is tested to 850 °C per IEC 60695-2-1. RoHS and REACH declarations are standard from Schneider Electric for this series.

MPN
LC1E1201F7