It switches 12 A in AC-3 / AC-3e duty up to 440 V, with a 380 V AC 60 Hz coil and one NC auxiliary contact built in.
There is no official successor listed in the lifecycle record; a parametric cross-reference would need to match the 380 V AC 60 Hz coil voltage and the 12 A AC-3 rating.
Mounts on DIN rail or plate. Dimensions are 45 mm wide, 74 mm high, 80 mm deep — fits standard 45 mm modular enclosure spacing. IP2X finger protection means it is safe for open-panel mounting but not washdown environments.
Compliant with EN/IEC 60947-1, -4-1, -5-1 and GB/T equivalents, plus EN/IEC 60335-1 Clause 30.2 and -2-40 Annex JJ for appliance applications. Operates without derating up to 3000 m altitude. Mechanical robustness rated for 3 Gn vibration closed, 10 Gn shock closed.