Schneider Electric LC1E120M5 — Contactors

Schneider LC1E120M5 Easy TeSys Control Contactor, 120 A, 3 Pole

MPNLC1E120M5
Obsolete

Schneider Easy TeSys Control LC1E120M5 contactor, 3-pole, 120 A, AC-3/AC-3e/AC-1, 220 V AC coil, 50 Hz, IP2X, DIN-rail/plate mount.

$128.02Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC1E120M5 — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationMotor control Resistive load
LC1E120M5 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-3 AC-3e AC-1
LC1E120M5 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1E120M5 — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068-2-30 test Db
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E120M5 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5
LC1E120M5 — Mechanical
ParameterValue
Width120 mm
Height158 mm
Depth132 mm

Product details

Overview

The LC1E120M5 is a Schneider Easy TeSys Control contactor, 3-pole normally open, rated 120 A in AC-3 utilization category at 440 V, with a 220 V AC 50 Hz coil. It carries EN/IEC 60947-4-1 and GB/T 14048.4 certifications, mounts on DIN rail or plate, and is rated IP2X per IEC 60529.

This contactor switches motor loads under AC-3 and AC-3e categories, handling the inrush and break of squirrel-cage motors up to 120 A. The AC-1 rating covers resistive loads at the same current. The coil pulls in at 220 V AC 50 Hz; the non-overlap time of 1.5 ms on energisation and de-energisation ensures NC and NO contacts never close simultaneously, preventing shoot-through in reversing or star-delta circuits.

Applications

Used in motor control centres, pump and fan panels, conveyor drives, and compressor starters where a 120 A, 3-pole contactor with AC-3 rating is required. Common in industrial and commercial building services across IEC markets.

MPN