This order code is marked obsolete by the manufacturer. There is no official successor order code in the lifecycle record, so a direct drop-in from the same brand is not documented. The form, fit, and function (3P, 120 A AC-3, 380 VAC coil, DIN-rail or plate mount) define the cross-reference search; any substitute must match those parameters and the mounting footprint.
Dimensions are 158 mm high, 120 mm wide, 132 mm deep — the depth is the dimension that projects from the mounting surface, so check enclosure depth clearance, especially in shallow gland-plate or door-mount scenarios. The IP2X finger protection means the contactor body is touch-safe but not sealed against dust or moisture; install inside a panel with at least an IP54 enclosure for industrial environments.
Standards and environmental limits
Fire resistance is 850 °C per IEC 60695-2-1. The TH protective treatment (pollution degree 3, tested to IEC 60068-2-30) means it withstands humid, cyclic condensation conditions typical of non-climate-controlled panels. No altitude derating needed up to 3000 m.