Skip to main content
Schneider Electric LC1E120Q6 — Contactors

Schneider LC1E120Q6 Easy TeSys Contactor, 120A AC-3, 380VAC

MPNLC1E120Q6
Active

Schneider Electric Easy TeSys Control, LC1E120Q6, 3P(3NO) contactor, AC-3/AC-3e ≤440V 120A/96A, 380V AC coil 60Hz, DIN-rail/plate mount.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC1E120Q6 — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationMotor control Resistive load

Ratings & Performance

LC1E120Q6 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-3 AC-3e AC-1

Contacts & Poles

LC1E120Q6 — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

LC1E120Q6 — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068-2-30 test Db
Fire resistance850 °C conforming to IEC 60695-2-1

Approvals

LC1E120Q6 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5

Mechanical

LC1E120Q6 — Mechanical
ParameterValue
Width120 mm
Height158 mm
Depth132 mm

Product details

The Schneider Electric LC1E120Q6 is a 3-pole contactor from the Easy TeSys Control range, rated 120 A in AC-3 duty (≤440 V) for switching motor loads, and 96 A in AC-3e for higher-efficiency motors. The 380 V AC 60 Hz coil pulls in reliably across the rated control voltage range. AC-3e extends that to energy-efficient motor designs with slightly different inrush profiles. AC-1 covers resistive loads at the same current level. The 132 mm depth fits standard enclosure depths without crowding the wiring gutter. Rated IP2X — finger-safe from the front, but the contactor is intended inside a panel or enclosure that provides the environmental seal.

Where it is used and sourcing reality

For a BOM line, the AC-3 current and coil voltage are the fit-critical parameters — confirm the 380 V 60 Hz coil matches your control transformer or line supply. EN/IEC 60947-4-1 and -5-1 compliance covers the contactor's motor-switching and control-circuit performance. GB/T equivalents apply for Chinese-market installations. Ambient range -20 to 70 °C at the coil, with -5 to 55 °C operation, covers typical indoor panel conditions.

Integration notes

Vibration tolerance: 1.5 Gn contacts open, 3 Gn closed, 5–300 Hz. Shock: 6 Gn open, 7 Gn closed. These numbers tell you the contactor holds its state under normal industrial vibration on a machine or in a truck-mounted panel. TH treatment per IEC 60068-2-30 (pollution degree 3) means the contactor is protected against condensation and high humidity environments — suitable for non-condensing indoor industrial use, but not rated for direct washdown.

Frequently asked questions

What is the closest alternative in the same family?

Within the Easy TeSys Control range, the LC1E series includes other current ratings and coil voltages. The LC1E120Q6 is the 120 A AC-3 variant with a 380 V 60 Hz coil. A sibling with a different coil voltage (e.g., 220 V 50/60 Hz or 24 VDC) would share the same mounting footprint and pole configuration, but the coil must match the control circuit.

What compliance documentation is available for this contactor?

The LC1E120Q6 is certified to EN/IEC 60947-1, -4-1, and -5-1, plus the corresponding GB/T standards. Fire resistance is tested to 850 °C per IEC 60695-2-1. The protective treatment meets TH (pollution degree 3) per IEC 60068-2-30. RoHS and REACH declarations are standard for Schneider Easy TeSys products, though specific certificates should be requested with the RFQ.

MPN