LC1E1210M6 — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationMotor control Resistive load
LC1E1210M6 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-3 AC-3e AC-1
LC1E1210M6 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1E1210M6 — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068-2-30 test Db
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E1210M6 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ
LC1E1210M6 — Mechanical
ParameterValue
Width45 mm
Height74 mm
Depth80 mm

Product details

The Schneider Electric LC1E1210M6 is a 3-pole (3NO) contactor from the Easy TeSys Control range, rated for 12 A in AC-3 and AC-3e utilisation categories at up to 440 V. AC-3 duty means it's sized for starting and stopping squirrel-cage motors — the 12 A rating covers motors up to roughly 5.5 kW at 400 V. The AC-3e rating adds an energy-efficiency classification for the same motor-switching profile.

Duty and application

Rated for both motor control and resistive load switching (AC-1), this contactor fits straightforward motor-starter duty in control panels. The 1.5 ms guaranteed non-overlap time between NC and NO contacts on both energisation and de-energisation means you can build interlocked reversing starters without external timing relays — the break-before-make window is built in. The 3000 m operating altitude without derating covers most installations outside high-mountain sites.

The IP2X finger protection on the contactor body is adequate for enclosed panels but not for exposed mounting. The TH protective treatment (pollution degree 3 per IEC 60068-2-30) means it handles humid, mildly corrosive environments common in industrial enclosures without conformal coating.

The 850 °C glow-wire test (IEC 60695-2-1) confirms flame resistance for the enclosure.

Frequently asked questions

What are the key ratings for this contactor?

Three-pole (3NO) contactor rated 12 A in AC-3/AC-3e at ≤440 V, with a 220 V AC 50/60 Hz coil and one N/O auxiliary contact. It also carries an AC-1 resistive load rating and a guaranteed 1.5 ms non-overlap time between NC and NO contacts.

What standards does the LC1E1210M6 comply with?

It conforms to EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, plus the Chinese GB/T 14048.1, 14048.4, and 14048.5. It also passes the 850 °C glow-wire test per IEC 60695-2-1.

How is this contactor mounted?

It mounts on DIN rail or directly to a backplate. The 45 mm width and 74 mm height fit standard panel layouts.

MPN