Skip to main content
Schneider Electric LC1E150ADCH2S260N — Contactors

Schneider Electric LC1E150ADCH2S260N Easy TeSys Contactor, 1

MPNLC1E150ADCH2S260N
Active

Schneider Electric Easy TeSys Control LC1E150ADCH2S260N, 1-pole DC contactor, Ith 150 A, coil 12 VDC.

$325.00Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LC1E150ADCH2S260N — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load
LC1E150ADCH2S260N — Contacts & Poles
ParameterValue
Pole configuration1P
LC1E150ADCH2S260N — Environmental
ParameterValue
IP degree of protectionIP60
Operating altitude13123.36 ft (4000 m) without derating
Mechanical robustnessVibrations 5 g, 10...500 Hz) Shocks 20 g for 11 ms)
LC1E150ADCH2S260N — Approvals
ParameterValue
StandardsIEC 60947-4-1 GB/T 14048.4
LC1E150ADCH2S260N — Mechanical
ParameterValue
Width2.3 in (58 mm)
Height2.9 in (74.3 mm)
Depth3.2 in (81.3 mm)

Product details

DC contactor with 150 A thermal current, 12 VDC coil

Coil is 12 V DC (Uc), with operational limits of 0.85 to 1.1 Uc and drop-out between 0.1 and 0.75 Uc. Hold-in power is 7.2 W. This variant is designed for resistive load switching at up to 1000 V DC maximum switching voltage. Ambient operating temperature span is -40 to 85 °C, with no derating up to 4000 m altitude. Rated insulation voltage (Ui) on the power circuit is 1500 V, impulse withstand (Uimp) 8 kV (coil not connected to power circuit). Compliance per IEC 60947-4-1 and GB/T 14048.4.

Mounting and termination notes

Mounts vertically on a support (vertical mounting support is specified). Overall dimensions: 3.2 in deep, 2.3 in wide, 2.9 in tall. Power circuit terminations use M8 bolt with flat and spring washers; tighten to 8–10 N·m (70.8–88.5 lbf·in). Control circuit comes with a 15.7 in (40 cm) two-wire pigtail. The contactor carries IP60 protection — dust-tight but not sealed against water ingress. Single-pole (1P) configuration: main pole is 1 NO, auxiliary contact is also 1 NO. Minimum switching conditions: 0.1 A and 8 V DC. Permissible short-time ratings: 150 A continuous, 170 A for 1000 s, 200 A for 360 s, 300 A for 60 s. On closing, operating time is 50 ms; on opening, 30 ms.

Frequently asked questions

What are the key ratings for this contactor?

The LC1E150ADCH2S260N is a 1-pole DC contactor rated for 150 A conventional free-air thermal current (Ith), with a 12 V DC coil and maximum switching voltage of 1000 V DC. Power circuit insulation voltage is 1500 V, impulse withstand 8 kV. Ambient operating temperature -40 to 85°C.

What are the mounting dimensions of the LC1E150ADCH2S260N?

Depth is 3.2 in (81.3 mm), width 2.3 in (58 mm), height 2.9 in (74.3 mm). It mounts vertically with M8 bolt terminations on the power circuit.

What compliance standards does this contactor meet?

It complies with IEC 60947-4-1 and GB/T 14048.4. Rated impulse withstand voltage is 8 kV (coil not connected to power circuit) and insulation resistance is 1000 MOhm at 1000 V DC.

MPN
LC1E150ADCH2S260N