Skip to main content
Schneider Electric LC1E160Q5 — Contactors

Schneider LC1E160Q5 Easy TeSys Contactor, 160A AC-3, 380V 50

MPNLC1E160Q5
Active

Schneider Electric Easy TeSys Control, LC1E160Q5, 3P(3NO) contactor, AC-3/AC-3e 160A ≤440V, 380V AC 50Hz coil.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC1E160Q5 — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationMotor control Resistive load

Ratings & Performance

LC1E160Q5 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-3 AC-3e AC-1

Contacts & Poles

LC1E160Q5 — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

LC1E160Q5 — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068-2-30 test Db
Fire resistance850 °C conforming to IEC 60695-2-1

Approvals

LC1E160Q5 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5

Mechanical

LC1E160Q5 — Mechanical
ParameterValue
Width120 mm
Height158 mm
Depth132 mm

Product details

Its headline rating is 160 A in AC-3 utilisation category at ≤440 V, meaning it switches three-phase induction motors up to that current under full load — the AC-3 rating is the one that governs motor starting and stopping, not the higher AC-1 resistive rating.

Mounts on either a DIN rail or a plate, giving flexibility for new builds or retrofit into existing enclosures. Dimensions are 158 mm high by 120 mm wide by 132 mm deep — measure the backpanel clearance, especially if the enclosure depth is tight. The IP2X degree of protection means the contactor is finger-safe but not sealed; it belongs inside a cabinet, not in a washdown zone.

Standards, environmental limits, and compliance

Operates without derating up to 3000 m altitude, and the permissible ambient range is -5 to 55 °C running, -20 to 70 °C at the coil terminals, with storage from -60 to 80 °C.

Frequently asked questions

What are the key ratings for this contactor?

160 A in AC-3 duty at ≤440 V, with a 380 V AC 50 Hz coil. It also carries AC-3e and AC-1 utilisation categories. The contactor is 3-pole, 3 normally-open.

What mounting options does the LC1E160Q5 support?

It mounts on either a DIN rail or a plate, giving flexibility for panel integration.

What compliance standards does this contactor meet?

It complies with EN/IEC 60947-1, -4-1, and -5-1, plus the corresponding GB/T standards. Fire resistance is tested to 850 °C per IEC 60695-2-1.

MPN