It is a 3-pole (3 NO) device rated 160 A in AC-3 utilization category at voltages up to 440 V, with a 380 V AC coil.
Mounts on DIN rail or plate, with dimensions 158 mm height, 120 mm width, and 132 mm depth — standard panel footprint for this class. The IP2X finger-safe front cover meets IEC 60529 for basic enclosure protection inside a control cabinet. Non-overlap time of 1.5 ms on both energisation and de-energisation ensures the NC and NO contacts never close simultaneously, critical for safety interlocks and reversing starter circuits.
Compliance & Environmental
Fire resistance rated to 850 °C per IEC 60695-2-1. Protective treatment TH (pollution degree 3) per IEC 60068-2-30 means it withstands humid, corrosive environments typical of industrial control rooms. Operating altitude 3000 m without derating, and ambient temperature range -20 to 70 °C at coil rated voltage, with storage from -60 to 80 °C.