Skip to main content
Schneider Electric LC1E18004N7IN — Contactors

Schneider Electric LC1E18004N7IN Easy TeSys Contactor, 4P, 4

MPNLC1E18004N7IN
Obsolete

Schneider Electric, Easy TeSys Control series, LC1E contactor, 4P (4NO), AC-1 utilisation category, 40 A rated at 415 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC1E18004N7IN — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load

Ratings & Performance

LC1E18004N7IN — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-1

Contacts & Poles

LC1E18004N7IN — Contacts & Poles
ParameterValue
Pole configuration4P

Environmental

LC1E18004N7IN — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068
Fire resistance850 °C conforming to IEC 60695-2-1

Approvals

LC1E18004N7IN — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5

Mechanical

LC1E18004N7IN — Mechanical
ParameterValue
Width45 mm
Height74 mm
Depth80 mm

Product details

Part identity and key ratings

The LC1E18004N7IN is a 4-pole (4NO) contactor from the Schneider Electric Easy TeSys Control range, rated for AC-1 resistive loads at 40 A up to 415 V.

The 4P configuration gives you four normally-open power poles, so you can switch a three-phase load plus a neutral, or gang two poles per phase for higher current. The non-overlap time of 1.5 ms between NC and NO contacts on both energisation and de-energisation is a safety feature — it guarantees that break-before-make timing, which matters in interlocking circuits where you can't have two contactors closed simultaneously.

Operating altitude rated to 3000 m, and the TH protective treatment (pollution degree 3) means it handles industrial atmospheres with some condensation or light contamination.

Frequently asked questions

What are the key ratings for this contactor?

It's a 4-pole (4NO) AC-1 contactor rated 40 A at 415 V, built to EN/IEC 60947-1, -4-1, and -5-1. The non-overlap time between NC and NO contacts is 1.5 ms on both energisation and de-energisation.

What compliance standards does this part meet?

It complies with EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and the Chinese GB/T 14048.1, 14048.4, and 14048.5. Fire resistance is 850 °C per IEC 60695-2-1.

How do I source an obsolete part like this?

Submit an RFQ. We can search surplus and broker channels for available inventory. Expect no factory support or warranty from the original manufacturer.

MPN