Schneider Electric LC1E18008Q7IN — Contactors

Schneider Electric LC1E18008Q7IN Easy TeSys Contactor, 4P, 4

MPNLC1E18008Q7IN
Obsolete

Schneider Electric Easy TeSys Control, LC1E18008Q7IN, 4P (2NO+2NC) contactor, AC-1 40A at ≤415V, 380V coil.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC1E18008Q7IN — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load

Ratings & Performance

LC1E18008Q7IN — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-1

Contacts & Poles

LC1E18008Q7IN — Contacts & Poles
ParameterValue
Pole configuration4P

Environmental

LC1E18008Q7IN — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068
Fire resistance850 °C conforming to IEC 60695-2-1

Approvals

LC1E18008Q7IN — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5

Mechanical

LC1E18008Q7IN — Mechanical
ParameterValue
Width45 mm
Height74 mm
Depth80 mm

Product details

Its AC-1 utilisation category rates it for 40 A at ≤415 V, making it suited for resistive load switching in control panels. The 380 V coil matches standard three-phase line voltages in many industrial installations.

This part is marked obsolete by the manufacturer. No official successor order code is listed, so any replacement would need to be qualified against the customer's approved manufacturer list (AML) before substitution.

The contactor carries compliance with EN/IEC 60947-1, 60947-4-1, and 60947-5-1, plus the Chinese GB/T equivalents — covering the main standard for low-voltage switchgear and controlgear, the specific contactor standard, and control circuit devices. Fire resistance is tested to 850 °C per IEC 60695-2-1. The protective treatment (TH) meets pollution degree 3 per IEC 60068, so it handles typical industrial atmospheres without derating.

The IP2X degree of protection means the contactor body is finger-safe but not sealed against moisture; install inside a panel with at least IP54 enclosure for washdown or outdoor areas. Operating altitude is rated to 3000 m without derating.

The AC-1 rating of 40 A at ≤415 V is the resistive load current — this is the current the contactor can make and break for heaters, lighting, or resistive banks. For motor loads (AC-3), the rating would be lower; no AC-3 figure is listed, so this part is not suited for motor switching.

Frequently asked questions

What are the key ratings for this contactor?

AC-1 rated 40 A at ≤415 V for resistive loads, with a 380 V coil. It is a 4-pole contactor configured 2NO+2NC.

How is this contactor mounted?

It mounts on a plate or DIN rail. The 45 mm width fits standard enclosure rail spacing, and the IP2X body is finger-safe for panel installation.

MPN