Skip to main content
Schneider Electric LC1E1801E7 — Contactors

Schneider LC1E1801E7 Easy TeSys Contactor, 18A, 48V AC Coil,

MPNLC1E1801E7
Obsolete

Schneider Electric Easy TeSys Control LC1E, 3-pole contactor, 18 A AC-3/AC-3e, 48 V AC 50/60 Hz coil, 1 NC auxiliary contact, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1E1801E7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationMotor control Resistive load
LC1E1801E7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-3 AC-3e AC-1
LC1E1801E7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1E1801E7 — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068-2-30 test Db
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E1801E7 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ
LC1E1801E7 — Mechanical
ParameterValue
Width45 mm
Height74 mm
Depth80 mm

Product details

Part overview and key ratings

The Schneider Electric LC1E1801E7 is a 3-pole contactor from the Easy TeSys Control range, rated 18 A in AC-3 duty at up to 440 V — meaning it switches three-phase motor loads up to that current under the standard motor-starting category. AC-3 and AC-3e utilisation categories cover squirrel-cage motor starting and plugging/reversing duty, while the AC-1 rating handles resistive loads.

Depth is 80 mm, which matters for enclosure depth clearance when wiring with ferruled conductors or routing the coil supply alongside the power circuit. The IP2X degree of protection means the contactor is finger-safe against accidental contact but is not sealed against moisture or dust — it belongs inside a panel, not exposed to washdown or outdoor conditions.

Also listed to EN/IEC 60335-1 Clause 30.2 and EN/IEC 60335-2-40 Annex JJ for appliance and HVAC applications. Operating altitude rated to 3000 m without derating.

Frequently asked questions

What is the LC1E1801E7's rated current and coil voltage?

Rated 18 A in AC-3/AC-3e duty up to 440 V, with a 48 V AC 50/60 Hz coil. It also carries an AC-1 resistive rating and is suitable for motor control and resistive load applications.

What standards does the LC1E1801E7 comply with?

Compliant with EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, GB/T 14048.1, GB/T 14048.4, GB/T 14048.5, and EN/IEC 60335-1 Clause 30.2 and EN/IEC 60335-2-40 Annex JJ. Fire resistance is 850 °C per IEC 60695-2-1.

How do I source the LC1E1801E7 if it is obsolete?

The part is sourced through independent or surplus channels. Submit an RFQ for a quote — it is not stocked as a standard production item and is quoted to order.

MPN
LC1E1801E7