Skip to main content
Schneider Electric LC1E1801M6 — Contactors

Schneider LC1E1801M6 Easy TeSys Contactor, 18A AC-3, 220V AC

MPNLC1E1801M6
Obsolete

Schneider Electric Easy TeSys Control contactor, 3P (3 NO), AC-3 18A at ≤440V, 220V AC coil, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1E1801M6 — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationMotor control Resistive load
LC1E1801M6 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-3 AC-3e AC-1
LC1E1801M6 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1E1801M6 — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068-2-30 test Db
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E1801M6 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ
LC1E1801M6 — Mechanical
ParameterValue
Width45 mm
Height74 mm
Depth80 mm

Product details

The Schneider Electric LC1E1801M6 is a 3-pole contactor from the Easy TeSys Control range, rated for 18 A in AC-3 utilisation category at up to 440 V. That AC-3 rating means it is designed for starting and stopping squirrel-cage motors — the most common motor-control duty — switching the load under full current. The 220 V AC coil is a standard control voltage for many industrial panels, so this part slots directly into existing 230 V control circuits without a transformer. It also carries an AC-1 rating for resistive loads, giving flexibility for heating or lighting banks, and an AC-3e rating for energy-efficient motors. The contactor is certified to EN/IEC 60947-4-1 (the main standard for contactors and motor-starters) and GB/T equivalents, plus EN/IEC 60335-1 for appliance safety — so it is accepted in both European and Chinese regulatory jurisdictions.

Operating altitude is 3000 m without derating, which covers most installations outside high-mountain sites. The contactor includes a guaranteed non-overlap time of 1.5 ms between NC and NO contacts on both energisation and de-energisation — a detail that matters for interlocking circuits where simultaneous closure could cause a short across the motor windings.

The TH protective treatment (pollution degree 3 per IEC 60068-2-30) means it withstands humid, tropical environments — a common requirement for HVAC or outdoor-adjacent panels. Fire resistance is tested to 850 °C per IEC 60695-2-1, which satisfies the glow-wire test for unattended appliances.

Frequently asked questions

What are the key ratings for this contactor?

It is a 3-pole contactor rated 18 A in AC-3 (motor) duty at up to 440 V, with a 220 V AC coil. It also carries AC-1 (resistive) and AC-3e ratings. The coil draws its rated current from the control circuit; verify the control transformer sizing for multiple contactors.

What compliance standards does the LC1E1801M6 meet?

It is certified to EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and the Chinese GB/T equivalents. It also meets EN/IEC 60335-1 Clause 30.2 and EN/IEC 60335-2-40 Annex JJ for appliance safety. Fire resistance is tested to 850 °C per IEC 60695-2-1.

What is the physical size and mounting of this contactor?

Dimensions are 45 mm wide, 74 mm high, and 80 mm deep. It mounts on a DIN rail or plate. The 45 mm width occupies one standard 2.5-module slot on a DIN rail.

MPN