Schneider LC1E1810E5 Easy TeSys Contactor, 18A AC-3, 48V 50H

MPNLC1E1810E5
Obsolete

Schneider Electric Easy TeSys Control LC1E, 3P contactor, 18 A AC-3/AC-3e ≤440 V, 48 V AC 50 Hz coil, 1 NO auxiliary contact.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1E1810E5 — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationMotor control Resistive load
LC1E1810E5 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-3 AC-3e AC-1
LC1E1810E5 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1E1810E5 — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068-2-30 test Db
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E1810E5 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ
LC1E1810E5 — Mechanical
ParameterValue
Width45 mm
Height74 mm
Depth80 mm

Product details

It carries 18 A in AC-3 duty (≤440 V) and uses a 48 V AC 50 Hz coil, with one normally open auxiliary contact built in. The contactor is rated for AC-3, AC-3e, and AC-1 utilisation categories, meaning it handles both motor starting (high inrush) and resistive heating loads. The AC-3e rating adds an energy-efficiency classification for motor switching. The IP2X finger-safe front and TH protective treatment (pollution degree 3) suit it for industrial control panels where condensation or mild contamination is expected.

No official successor order code is listed in the lifecycle record, so a parametric cross-reference is needed to find a form-fit-function equivalent.

The 48 V AC 50 Hz coil is a specific control voltage. If your panel uses 24 V DC or 110 V AC control, this coil won't pull in — verify the control circuit voltage before specifying. The contactor is certified to EN/IEC 60947-4-1 (the main contactor standard) and EN/IEC 60947-5-1 (auxiliary contacts), plus GB/T equivalents for Chinese markets. Fire resistance to 850 °C per IEC 60695-2-1 is built in.

Frequently asked questions

What are the key ratings of the LC1E1810E5?

It is a 3-pole contactor rated 18 A in AC-3/AC-3e duty at ≤440 V, with a 48 V AC 50 Hz coil and one normally open auxiliary contact. It also covers AC-1 resistive loads.

How do I source the LC1E1810E5?

Since it is obsolete, it is sourced to order against an RFQ through surplus or broker channels. No official replacement order code is provided.

MPN
LC1E1810E5